Communication data, 4technical data – Lenze MC-PND Benutzerhandbuch

Seite 36

Advertising
background image

4

Technical data

Communication data

LDCDS−MC−PNx DE/EN 2.0

36

l

H1_Daten−E−Daten MC−PND

Communication data

MC−PNC (controller)

I/O data

l

Configurable up to max. 5760 bytes input

l

Configurable up to max. 5760 bytes output

Data transport

l

Ethernet frames

Communication

l

PROFINET IO−RT
– cyclic and acyclic

Acyclic data

l

Read, write, record: max. 1 kbyte/request

l

Alarms

Functions

l

Cyclic process data

l

Buffering host−controlled data exchange of cyclic
data

l

Minimum cycle time: 1 ms

l

Different cycle times are configurable for different
devices

l

Max. 32 devices can be configured

l

DCP

l

Context management via CL−RPC

l

One buffer is available per device for diagnostic
data

Special features

l

No support for
– RT over UDP
– Multicast communication
– DHCP

l

Only one IOCR1 per IO device is possible, IOCR data
length: 1024 bytes

l

Max. number of the connectable IO devices
decreases to 25 when cycle times lower than 4 ms
are used.

l

NameOfStation of the IO controller cannot be set
via the DCP Set NameOfStation service but only by
the configuration during the start