5 emergency circuit isolation method, 6 total circuit isolation method, 7 grounding the generator – Generac Power Systems 004917-2 User Manual

Page 12: 8 generator ac neutral connections, 9 transfer switch signal connections

Advertising
background image

10 Generac

®

Power Systems, Inc.

Figure 2.1 – Basic Standby Electric System

2.5

EMERGENCY CIRCUIT ISOLATION
METHOD

This prevents overloading the generator by keeping
electrical loads below the wattage/amperage capacity
of the generator. If the generator is powering only crit-
ical loads, within the wattage/amperage capacity, dur-
ing utility power outages, consider using the emer-
gency circuit isolation method.

Critical electrical loads are grouped together and
wired into a separate “Emergency Distribution
Panel.” Load circuits powered by that panel are with-
in the wattage/amperage capacity of the generator set.
When this method is used, it is difficult to overload
the generator. The transfer switch must meet the fol-
lowing requirements:

• It must have an ampere rating equal to the total

amperage rating of the emergency distribution
panel circuit.

• Have it installed between the building’s main dis-

tribution panel and the emergency distribution
panel.

2.6

TOTAL CIRCUIT ISOLATION
METHOD

When a generator capable of powering all electrical
loads in the circuit is to be installed, use the “Total
Circuit Isolation Method.” It is possible for the gener-
ator to be overloaded when this isolation method is
employed. The following apply to the transfer switch
in this type of system.

• Ampere rating of the transfer switch must equal

the ampere rating of the normal incoming utility
service.

• The transfer switch is installed between the utility

service entrance and the building distribution
panel.

2.7

GROUNDING THE GENERATOR

The National Electrical Code requires the frame and
external electrically conductive parts of this equip-
ment to be properly connected to an approved earth
ground and/or grounding rods. For that purpose, a
GROUND LUG (Figure 2.2) is provided on the gener-
ator mounting base. Consult a qualified electrician
for grounding requirements in the area. Grounding
procedures must meet local regulations.

Do not connect the ground wire to any pipe
that carries a flammable or explosive substance
– FIRE or an EXPLOSION may result.

Proper grounding helps protect personnel against
electrical shock in the event of a ground fault condi-
tion in the generator or in connected electrical
devices. In addition, grounding helps dissipate static
electricity that often builds up in ungrounded
devices.

Figure 2.2 – Generator Grounding Lug (typical)

2.8

GENERATOR AC NEUTRAL
CONNECTIONS

Generac uses an UNGROUNDED AC neutral.
Grounding is recommended only at the main service
entrance. If the neutral wire is grounded and one of
the phase loads becomes grounded, the excessive
current opens the load circuit breaker or collapses
the generator field. The actual result depends on the
electrical characteristics of the particular installed
generator.

2.9

TRANSFER SWITCH SIGNAL
CONNECTIONS

2.9.1 PRE-PACKAGED ATS

If the generator is to be installed with a pre-packaged
transfer switch, it is necessary to connect the control
wires to the generator and set position two of the
four-position dip switch to OFF.

‹

GROUNDING

LUG

DANGER

Section 2 — Installation

QUIETSOURCE

Liquid-cooled 30 kW Generators

Advertising