VEGA VEGABAR 61 Foundation Fieldbus Benutzerhandbuch

Seite 64

Advertising
background image

Secondary_value_2

scale_in_0

scale_in_100

Sensor_value

0 %

100 %

bar

0,500

-0,500

0

%

100

%

scale_in_100

scale_in_0

Abb. 30: Abgleich VEGABAR 61

Parameterliste
Die folgende Liste enthält die wichtigsten Parameter und ihre Bedeutung:

l

primary_value

-

Process Value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'C

hannel' = 1. Unit derives from 'Primary_value_unit'

l

primary_value_unit

-

Unit code of 'Primary_value'

-

%

l

secondary_value_1

-

Process pressure. Selected as input to AIFB by setting 'Channel' = 2. Unit derives from
'S

econdary_value_1_unit'

l

secondary_value_1_unit

-

Unit code of 'Secondary_value_1'

-

bar, PSI, …, m, ft, …; in case of length type engineering unit and access to parameters the
corresponding values will be converted by density factor

l

secondary_value_2

-

Value after min/max-adjustment. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'

l

secondary_value_2_unit

-

Selected unit code for "secondary_value_2"

l

sensor_value

-

Raw sensor value, i.e. the uncalibrated measurement value from the sensor. Unit derives from
'S

ensor_range.unit'

64

VEGABAR 61 • Foundation Fieldbus

10 A

nhang

28258

-DE

-081118

Advertising