VEGA VEGASON 66 Foundation Fieldbus Benutzerhandbuch

Seite 57

Advertising
background image

l

CAL_LEVEL_HI

-

Min./max.-adjustment: Level at 'Cal_point_hi'. When writing 'Cal_level_hi' and 'Cal_-

type' = 1 (Online) the 'Cal_point_hi' is automatically set to the current sensor value. The

unit is defined in 'Level_unit'

l

CAL_LEVEL_LO

-

Min./max.-adjustment: Level at 'Cal_point_lo'. When writing 'Cal_level_lo' and 'Cal_-

type' = 1 (Online), the 'Cal_point_lo' is automatically set to the current sensor value. The

unit is defined in 'Level_unit'

l

CAL_TYPE

-

Min./max.-adjustment: Defines type of calibration: Dry: no influence of sensor value.

Online: current sensor value determines 'Cal_point_hi/lo'

l

level

-

Value after min/max-adjustment

l

level_unit

-

Unit code of 'Level', 'Level_offset', 'Cal_level_hi', 'Cal_level_lo'

l

level_offset

-

Offset that is added to the 'Level' value. Unit derives from 'Level_unit'

l

SENSOR_OFFSET

-

Offset that is added to the 'Sensor_value'. Unit derives from 'Sensor_range.unit'

l

end_of_operation_range

-

Set up to suit the process conditions

l

begin_of_operation_range

-

Set up to suit the process conditions

l

product_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

liquids_medium_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

solids_medium_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

liquids_vessel_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

solids_vessel_type

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written

l

fast_level_change

-

Set up to suit the process conditions. If Special-Parameter adjustment has been utilized

this parameter cannot be written