Electricial Characteristics

Physicial Layer Type

Low-power signaling, bus-po-

wered, FISCO I.S.

Input Impedance

> 3000 Ohms between

7.8 KHz - 39 KHz

Unbalanced Capacitance

< 250 pF to ground from either

input terminal

Output Amplitude

0.8 V P-P

Electrical Connection

2 Wire

Polarity Insensitive

Yes

Max. Current Load

10 mA

Device minimum operating voltage

9 V

Transmitter Function Blocks

Resource Block (RB)

1

Transducer Block (TB)

1

Standard Block (AI)

3

Execution Time

30 mS

Advanced Function Blocks

Discret Input (DI)

Yes

PID Control

Yes

Output Splitter (OS)

Yes

Signal Characterizer (SC)

Yes

Integrator

Yes

Input Selector (IS)

Yes

Arithmetic (AR)

Yes

Diagnostics

Standard

Yes

Advanced

Yes

Performance

No

Function Blocks Instantiable

No

General Information

LAS (Link Active Scheduler)

Yes

Master Capable

Yes

Number of VCRs (Virtual Communication Re-

lationships)

24