Funktionsblock analog input (ai) – VEGA WEIGHTRAC 31 Foundation Fieldbus Benutzerhandbuch

Seite 71

Advertising
background image

71

11 Anhang

WEIGHTRAC 31 • Foundation Fieldbus

42375-DE-131119

Revisions Data

DD-Revision

Rev_01

CFF-File

010101.cff

Device Revision

0101.ffo
0101.sym

Cff-Revision

xx xx 01

Device-Softwarerevision

> 1.5.0

ITK (Interoperability Test Kit) Number

6.0.1

Electricial Characteristics

Physicial Layer Type

Low-power signaling, bus-powe-

red, FISCO I.S.

Input Impedance

> 3000 Ohms between 7.8 KHz -

39 KHz

Unbalanced Capacitance

< 250 pF to ground from either in-

put terminal

Output Amplitude

0.8 V P-P

Electrical Connection

4 Wire

Polarity Insensitive

Yes

Max. Current Load

10 mA

Device minimum operating voltage

9 V

Transmitter Function Blocks

Resource Block (RB)

1

Transducer Block (TB)

1

Standard Block (AI)

3

Execution Time

30 ms

Diagnostics

Standard

Yes

Advanced

Yes

Performance

No

Function Blocks Instantiable

No

General Information

LAS (Link Active Scheduler)

No

Master Capable

No

Number of VCRs (Virtual Communication

Relationships)

24

Funktionsblock Analog Input (AI)

Der Funktionsblock "Analog Input (AI)" nimmt den originären Messwert ausgewählt durch eine

Channel Number und stellt ihn an seinem Ausgang für weitere Funktionsblöcke zur Verfügung.