upply and signal circuit

Terminal no. 1[+], no. 2[-]

In ignition protection type intrinsic safety EEx ia
IIC/IIB
Only for connection to a certified intrinsically
safe circuit.
Maximum values:
Ui = 20 V

Ii = 103 mA

Pi = 516 mW

Li = negligibly small

Ci = negligibly small

The intrinsically safe circuits are electrically separated from parts which can be grounded.

For applications requiring instruments of category 2G or 1/2G, the intrinsically safe power
supply and signal circuit can correspond to protection class ia or ib. For connection to a circuit
of category ib, the ignition protection type identification is EEx ib IIC T6.

T

ip:

Ignition protection type identification: II 2G EEx ia IIB T6, II 2G EEx ib IIB T6 resp. II 1/
2G EE

x ia IIB T6 in case of power supply via a circuit of group IIB.

3

.2 A

pplication conditions

3

.2.1

P

ermissible ambient temperatures

O

n the sensor - category 1/2G

Temperature class

-

T6

-20 … +85 °C

-

T5

-20 … +100 °C

-

T4

-20 … +135 °C

-

T3 without temperature adapter

-20 … +150 °C

-

T3 with temperature adapter

-20 … +200 °C

-

T2, T1 with temperature adapter

-20 … +250 °C

O

n the sensor - category 2G

Temperature class

-

T6

-40 … +85 °C

-

T5

-40 … +100 °C

-

T4

-40 … +135 °C

-

T3 without temperature adapter

-40 … +150 °C

6