KROHNE DK 32-DK 34 Reed L Ex II2G DE Benutzerhandbuch

Seite 2

Advertising
background image

07/2009

MA DK-Reed-L-Ex-II2G-AD-R02-de-en

4000408202

Reed Contact unit to mount on DK32 / DK34

Manual

Electrical equipment for explosive hazardous areas

Equipment Category

II 2 G to use in explosive hazardous areas zone 1

Declaration of Conformity

The electrical equipment operates as a simple device. It is in

conformity with intrinsic safety EN 60079-11:2007, para. 5.7

Ex- Marking

none (because it isn’t required in accordance to 60079-11, para. 5.7)

Reed-contact type

Bistable contact with an intal tension magnet

Operating temperature range

-20°C to +120°C

-20°C to +200°C (HT- design)

Isolation

500 Vac to Earth

Electrical data

Only for connection on certified intrinsically safe circuits,

Maximum values:

Ui = 30 V

Ii = 100 mA

Ci negligible

Li negligible

Temperature class

T6, maximum operating temperature 40°C

T5, maximum operating temperature 55°C

T4, maximum operating temperature 90°C

T3, maximum operating temperature 155°C

T2, maximum operating temperature 200°C

Electrical connection

FEP coated connection cable

Terminal

assignment

br = brown

bl

=

blue

rt = red

General

Install and operate the device in accordance with the operating instruction

Installation,

Starting

Requirements

Statutes, recommendation, engineering standards for application have to be
kept. The warrant of intrinsic safety is only by interconnection with
intrinsically safe equipment.
To prevent risk of flammable hazard in case of malfunctions and or transient
in system with equipotential bonding system, use galvanic separation for
(connected) supplying or switching equipment.


Maintenance, Service

No modifications on equipment in explosive hazardous areas are permitted.

rt

bl

br

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: