6.2 Model DIH10-Ex connection

The 4-pin terminal block for the connection of the current-loop display

is located on the rear of the display and is accessible once the case is

open.

Terminal 1: Positive terminal of the current loop

Terminal 2: Negative terminal of the current loop

Terminals 3 and 4 are connected together on the PCB and enable the

convenient connection of a transmitter built into the connection head.

Con-

trollers

Ex area

Transmitter

supply isolator

Maximum terminal voltage: DC 30 V

Maximum current: 100 mA

Voltage drop: 3.2 V

Maximum power: 1 W