Operating Instructions Safety Switches SGP..AS1

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

Figure 3: Opening the safety switch

Functional check

Warning! Danger of fatal injury as a result of faults
in installation and functional check.

Before carrying out the functional check, make
sure that there are no persons in the danger
area. Observe the valid accident prevention
regulations.

After installation and any fault, the safety function must
be fully checked. Proceed as follows:

f

Mechanical function test

The actuator must slide easily into the actuating head.
Close the safety guard several times to check the
function.

f

Electrical function test

1. Switch on operating voltage.
2. Close all safety guards.

f

The machine must not start automatically.

3. Enable operation in the control system.
4. Open the safety guard.

f

The machine must switch off and it must not be
possible to start it as long as the safety guard is
open.

Repeat steps 2 - 4 for each safety guard.

Inspection and service

If damage or wear is found, the complete switch
and actuator assembly must be replaced.

Replacement of individual parts or assemblies
is not permitted!

Note: The year of manufacture can be seen in the
bottom, right corner of the rating plate.

No servicing is required, but regular inspection of
the following is necessary to ensure trouble-free long-
term operation:

f

correct switching function

f

secure mounting of components

f

dirt and wear

f

loose plug connectors.

Subject to technical modifications; no r

e

sponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

099194-03-10/11 (translation of the original operating instructions)

Exclusion of liability under the following
circumstances

f

incorrect use

f

non-compliance with safety regulations

f

installation and electrical connection not performed
by authorized personnel

f

failure to perform functional checks.

EC declaration of conformity

The manufacturer named below herewith declares that
the product fulfills the provisions of the directive(s)
listed below and that the related standards have been
applied.

EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany

Directives applied:

f

Machinery directive 2006/42/EC

Standards applied:

f

EN 60947-5-1:2004 + Cor.:2005 + A1:2009

f

EN 1088:1995+A2:2008

Leinfelden, July 2010

Dipl.-Ing. Michael Euchner
Director

Duc Binh Nguyen
Authorized representative empowered to draw up
documentation

The signed EC declaration of conformity is included
with the product.

Technical data

Parameters

Value

Housing material

Reinforced thermoplastic

Deg. of prot. acc. to IEC 60529 IP 67, mating connector plugged
Mechanical life

2x10

6

operations

Ambient temperature

-20 ... +55°C

Installation position

Any

Approach speed, max.

20 m/min

Actuating force

25 N

Actuation frequency, max.

6,700/h

Extraction force

25 N

Retention force

10 N

Switching principle

2 positively driven NC contacts, slow-
action switching contact

EMC protection requirements

Acc. to EN 50295 (AS-Interface
standard) and IEC 62026

Connection

M12 plug connector

AS-Interface data acc. to

EA code: 7

AS-Interface specification 2.1

ID code: B

Total current consumption, max. 45 mA
Valid AS-Interface addresses

1 - 31

AS-Interface inputs

Acc. to AS-Interface Safety at Work

Positively driven NC contact 1

D0, D1

Positively driven NC contact 2

D2, D3

AS-Interface outputs
D1

Red LED, 1 = LED on

D2

Green LED, 1 = LED on

AS-Interface LED Power

Green, AS-Interface voltage present

AS-Interface LED Fault

Red, offline phase or address 0

Reliability values according to EN ISO 13849-1
B

10d

3 x 10

6

Status table

Programming

State

D0, D1

D2, D3

Monitor diagnosis

Green

Safety guard closed

Code sequence

If start-up test selected:

yellow flashing on start-up

2-channel

Intermediate state during opening or closing

dependent

of the safety guard.

Half-seq.

00

During opening: yellow flashing

Synchronization time

Switch S1 (internal) open

During closing: red

3 s

Intermediate state during opening or closing

After expiration of the synchronization time:

of the safety guard.

00

Half-seq.

yellow flashing

Switch S2 (internal) open

Safety guard open

00

00

Red

Address 0 or communication disrupted

Gray