Dial/ contact dial thermometers, 4 installation, 5 operation – JUMO 60.8425 Contact dial thermometer with slow-break/magnetic snap-action contact Operating Manual Benutzerhandbuch

Seite 2: 1 general, 2 description, 3 electrical connection

Advertising
background image

Dial/

Contact dial

thermometers

Class 1

with slow-break/

magnetic snap-action

contact

B 60.8425.0.1

Operating

Instructions

09.05/00403311

4 Installation

Ambient temperatures

Dial thermometers exhibit the highest measurement accuracy at an ambient
temperature of +23°C at the case and capillary. Other ambient temperatures
will lead to indication errors. The corresponding influence on the housing or
capillary and the permissible ambient temperatures for storage and transport
can be taken from the appropriate data sheet.

Nominal operating position

any

Arrangement of the capillary

❏ The capillary should not be run closely to sources of cold or heat.
❏ Protect the capillary from possible damage.
❏ Kinks or breaks in the capillary will disable the instrument.

❏ If the probe is subject to shock and vibration, the capillary should be

arranged in several loops between the last fixing point and the probe, so
that it can swing freely.

Probe installation

The temperature probe must be
so installed that its active portion
(marked length L) is completely
immersed in the medium to be
measured, otherwise a measure-
ment error will occur.
When deciding on the temperature probe location, the temperature distribu-
tion in the medium has to be taken into account.
When using protective pockets, the heat transfer resistance between the out-
side of the probe and the inner wall of the pocket can be reduced by filling it
with a thermal contact medium.

5 Operation

Setpoint adjustment

Setpoints can be adjusted by means of the rotary knob in the center of the
window.
With version “Setpoint adjustment by key”, the setpoints can be adjusted
through the adjustment lock (key is with the terminal box).

Indication correction

If the ambient temperature at the case and capillary deviates from the calib-
ration temperature (+23°C), there is a permanent error at constant ambient
temperatures, or a variable error under changing ambient temperatures, see
Installation/Ambient temperatures.
Dial thermometers with indication correction can be adjusted at constant am-
bient temperatures. The adjustment is made on the back using a screwdriver,
after removal of the closing plug.

Caution

❏ Do not expose the dial thermometer directly to corrosive

media. Take the protection rating into account when instal-
ling.

❏ If the thermometer is subject to strong shock and vibration, this

will impair the function and life of the instrument. The installation
site should therefore be largely free from vibration.

Minimum bending radius: 50 mm

hex

1 General

JUMO GmbH & Co. KG is a company which is certified according to ISO
9001. You have purchased a product which meets high requirements and ful-
fils, or surpasses, all the specifications listed.
Nevertheless, if you have any reason for complaint, please return the instru-
ment to us, with a detailed description of the fault you have observed.
These operating instructions do not cover all conceivable applications. So if
you cannot find advice on your particular task, please contact the nearest
subsidiary or the main factory.
None of the dial thermometers described in these operating instructions re-
quires any maintenance. They do not contain any components that can be re-
paired or replaced by the user. Repairs can only be carried out in the factory!

Please read these Operating Instructions before commissioning the
instrument.
Please assist us to improve these instructions, where necessary.
Your suggestions will be appreciated.
Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

If any difficulties should still arise during start-up, please do not un-
dertake any unauthorized manipulations on the instrument. This will
endanger your rights under the instrument warranty!
Please contact your supplier or the main factory in such a case.

2 Description

Dial thermometers with rigid stem or capillary are filled with an organic liquid
or with gas, and operate on the principle of liquid expansion or pressure
change. The resulting movement is converted into a rotation of the pointer,
without any gearing.
The built-in electrical limit signal contact (slow-break or magnetic snap-action
contact) is an auxiliary circuit switch which, depending on the direction of the
movement, opens or closes an electrical circuit at the set limits, by means of
a contact arm moving with the pointer.
Provided you observe the instructions below, you can be sure of problem-free
operation.

Accessories

The necessary accessories are inside a bag which is enclosed together with
the thermometer. Please check the package carefully!

3 Electrical connection

Wire up in accordance with the connection diagram (nameplate)!

Assembly of the terminal box

6-pole with earth terminal, conductor cross-section up to 2.5 mm

2

, suitable

for cable diameters 6.5 to 13 mm.

Recommended contact loading

Limits for contact loading

Danger

With dangerous measurement media such as oxygen, acetylene,
flammable and toxic substances, as well as in refrigeration equip-
ment, pressure vessels etc., the relevant regulations and require-
ments must be observed.

Danger
The electrical connection must only be carried out by qualified per-
sonnel.

The enclosure protection specified will only be achieved if the cable/
terminal box is mounted correctly.

0

( 1 ) Cover screw (captive)

0

( 2 ) Cover

0

( 3 ) Funnel-shaped guide

0( 3 )

for adjustment key

0

( 4 ) Sealing ring

0

( 5 ) Screw-in gland

0

( 6 ) Pressure washer

0

( 7 ) Grooved ring

0

( 8 ) Clamping cage

0

( 9 ) Middle section

( 10 ) Sealing ring

( 11 ) Bottom section

( 12 ) Shaped seal

Voltage

AC / DC

Slow-break contact

Magnetic snap-action contact

resistive

load

inductive

load

resistive

load

inductive

load

V

AC

mA

DC
mA

p.f. > 0.7

mA

AC

mA

DC
mA

p.f. > 0.7

mA

230 / 220

0

40

0

45

0

25

100

120

0

65

110

0

80

0

90

0

45

200

240

130

0

48

120

170

0

70

300

450

200

0

24

200

350

100

400

600

250

Slow-break contact

Magnetic snap-action contact

Max. values

Min. values

Max. values

Min. values

for contact loading with resistive load

Nom. operating
voltage U

r.m.s

250 V

24 V

250 V

24 V

Nom. operating
current:

switch-on curr.
switch-off curr.
cont. current

0.7 A
0.7 A
0.6 A

- - -

1.0 A
1.0 A
0.6 A

- - -

Contact rating

10 W / 18 VA

0.4 W / 0.4 VA

30 W / 50 V

0.4 W / 0.4 VA

JUMO GmbH & Co. KG

Delivery address: Moritz-Juchheim-Straße 1

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 60 03-0

Fax:

+49 661 60 03-6 07

e-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.

JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2TT, UK
Phone: +44 12 79 63 55 33
Fax:

+44 12 79 63 52 62

e-mail: [email protected]
Internet: www.jumo.co.uk

JUMO PROCESS CONTROL INC.

8 Technology Boulevard
Canastota, NY 13032, USA
Phone:

315-697-5866
1-800-554-JUMO

Fax:

315-697-5867

E-mail:

[email protected]

Internet: www.jumo.us

Advertising