Electrical installation

LDCDS−MC−CAN2 DE/EN 3.0

30

l

H1_E_INST−Hin_Treiber−Install

Specification of the transmission cable

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W

(95 ... 140

W

)

Cable resistance/cross−section

Cable length

£

300 m

£

70 m

W

/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£

40 m

W

/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£

5 ns/m

)

Note!

For commissioning the unit, the corresponding driver has to be installed on the
Industrial PC. It can be found on the DVD from the scope of supply of the
standard device ("PC−based automation" or "Controller−based automation").