Optische Sensoren / Photoelectric Sensors


Seite 12

www.baumer.com

Outputs:

Analog output
Two sensor versions are available: with voltage output 0 … 10 V or current output 4 … 20 mA.

Alarm output (active high)
As long as there is an object within the actual - taught - measuring range and the signal received is
sufficiently strong the output is low.
If there is no object inside the actual - taught - measuring range or the signal received is of
insufficient strength or quality the alarm output is high.


Functions:

Every sensor is delivered with the factory setup (max. measuring range). The teach-in feature was
designed to choose a smaller range within the nominal measuring range for optimizing the
resolution. Output current, voltage and alarm output adapt to the new range. Two positions must be
taught.

The first teach-in position aligns with 0 V (or 4 mA), the second position aligns with 10 V (or 20

mA)

These teach-in positions are always just at the border of the new range (inside the measuring

range)

The sensor may be taught more than 10,000 times in its lifetime

The sensor can always be reset to the factory settings

The sensor may be taught using the teach button or via the external teach input

During the teach-in process, the red LED and the alarm output provides a feedback

The red LED on the back side of the sensor and the alarm output indicate “run” mode if an object

is within the measuring range.



Attention:
Within 5 minutes after power on, the sensor can be taught using the button or the teach-in wire.
After 5 minutes, the teach-in button will be locked preventing accidental adjustment. The teach-in
wire is active all the time.

0.2 m

4 m

4mA

2mA

Analog out

20 mA

Example of
a taught
output
curve

Alarm out

LED

Standard
output
curve

0.2 m

4 m

4mA

2mA

Analog out

20 mA

Example of a
revers taught
output curve

Alarm out

LED

Standard
output
curve

0.2 m

4 m

0 V

Analog out

10 V

Example of a
revers taught
output curve

Alarm out

LED

Standard output
curve

0.2 m

4 m

0V

Analog out

10 V

Example of a
taught output
curve

Alarm out

LED

Standard output
curve