H3C Technologies H3C S5800 Series Switches Benutzerhandbuch

Seite 9

Advertising
background image

5

Warning: The unit must be permanently connected to the protective ground before operation. The
cross-sectional area of the protective earthing / grounding conductor shall be as specified in the

following table:
Warnung: Die Anlage muss vor der Inbetriebnahme ständig an die Schutzerde geleitet werden.

Die Querschnittsfläche des Schutzerdungsleiters soll in der folgenden Tabelle genau
aufgezeichnet werden:
警告:设备操作前必须永久接地。接地线线径请参考下面表格:

Equipment Model
Modell der Anlage
设备型号

Minimum cross-sectional area
Mindestquerschnitt
导线最小截面积

mm

2

AWG

H3C S5800-54S

2.5

12

H3C S5800-32C-PWR
H3C S5800-56C-PWR,
H3C S5800-60C-PWR

1.0 16

Others 0.75

18

For the equipment with Power Supply YM-2651B, PSR650B-12A1, PSR750-A, PA-2521-1H, GPL520-ADH,
HPSL520-AD, the power cord set must be approved for the country where it is used:
Für die Ausstattung mit Netzteil YM-2651B, PSR650B-12A1, PSR750-A, PA-2521-1H, GPL520-ADH,

HPSL520-AD, das Netzkabel muss für das Land, in dem es verwendet wird, zugelassen werden:

如果设备使用

YM-2651B, PSR650B-12A1, PSR750-A, PA-2521-1H, GPL520-ADH, HPSL520-AD 电源,

电源线的使用必须满足下面国家列表的要求:

Warning Power Cord Table:
The power cord set must be approved for the country where it is used.
WARNUNG Netzkabel Tabelle:
Das Netzkabel muss für das Land, in dem es verwendet wird, zugelassen werden.
警告:电源线表格:

电源线组件必须满足使用的国家认证要求。

U.S.A. and
Canada

The cord set must be UL approved and CSA certified

The minimum specification for the flexible cord is:

No. 18 AWG

Type SV / SVT or SJ / SJT or SPT-2

3 conductor.

The cord set must have a rated current carrying capacity of at least 10A.

The attachment plug must be an earth-grounding type with a NEMA

5-15P (15A, 125V) or NEMA 6-15P (15A, 250V) configuration

United Kingdom

The supply plug must comply with BS1363 (3-pin, 13A) and be fitted with

a 13A fuse that complies with BS1362

The mains cord must <HAR> or <BASEC> marked and be of type

H03VVF3G1.0 (minimum).

Europe

The supply plug must comply with CEE 7/7 (“SCHUKO”)

The mains cord must <HAR> or <BASEC> marked and be of type

H05VVF3G1.0 (minimum)