EC2-IR__65046__R01.doc Rev.: 01

Replacement for Rev.:00

2 / 4

20.07.2007

Infrared Remote Control for EC2

Operating Instructions

GB

HOW TO USE THE REMOTE CONTROL UNIT

Access without code

1) HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE
CONTROL UNIT TRANSMISSION

press the 'ENABLE' button to operate the remote control unit;

the controller's led indicator above the digits flashes and the first
parameter - '/C' - is immediately displayed. If the display shows a
code different from /C, it is necessary to introduce the access
code (see point 5 below).

2) MODIFYING THE MAIN PARAMETERS

press either the + or - key relative to the parameter you want to

modify. The display will show the code of the selected
parameter
(see the codes of the parameters listed in the
Instruction Sheet of the instrument). Press the button again to
display the value associated to the selected parameter and

press

+ to increase it;

press

- to decrease it.

The section including directly accessible buttons also comprises 3 buttons
that activate/deactivate the function they represent:
DEFROSTING SECTION:

START activates/deactivates a manual defrosting cycle;

evap.tmp displays the temperature value measured by the evaporator

probe (if present) or the value measured by the second probe
(Thermometer EC2-000).

Important: This function is always active. Consequently the
temperature measured by the second probe will be always
displayed without having to press the 'START' button or
select the access code (see point 5 below).

CONTINUOUS CYCLE SECTION:

C.cycle. activates a continuous cycle;

see point 4 below to exit the programming procedure.

3) HOW TO MODIFY THE PARAMETERS NOT DIRECTLY INDICATED
BY A SPECIFIC BUTTON
The other parameters - not directly associated to a specific button on the
remote control unit - can be easily modified as follows:

perform the same operations described in point 1 above until the

first parameter '/C' appears on the display;

3.1

press either

or until the display shows the parameter you

want to modify;

press

SEL to display the value of the selected parameter;

press

either or

to increase/decrease its value;

press

SEL to confirm temporarily the new value and display again

the code of the parameter;

to modify another parameter repeat the operations described

above starting from point 3.1;

see point 4 below to exit the programming procedure.

4) HOW TO EXIT THE PROGRAMMING PROCEDURE

press

PRG to exit and memorize all modifications;

press ESC to exit without memorizing the previous

modifications;

do not press any button for at least 60 seconds (TIME OUT).

In this way the previous modifications will be cancelled.

Access with code

5) HOW TO ENABLE THE CONTROLLER TO RECEIVE THE REMOTE
CONTROL UNIT TRANSMISSION

press

'ENABLE' to operate the remote control unit;

all the controllers exposed to the beam of the remote control unit

will display their own access code;

select the access code of the controller whose parameter you

intend to modify using the numeric section on the remote control
unit. Select the code correctly (if the code of the controller is 05,
press 0 and 5).

the controller's led indicator above the digits flashes and,

simultaneously, the code of the first parameter '/C' appears on the
display.

perform the same operations described in point 2) or 3)

above.

HOW TO SELECT THE ACCESS CODE
SETTING THE ACCESS CODE
All EC2 controllers have no factory-set access codes. The User can
choose and set his own access codes by simply modifying the H3
parameter as follows:

press

'ENABLE' to operate the remote control unit;

the controller's led indicator above the digits flashes and the first

parameter ('/C) appears immediately.

press to display the H3 parameter;

press

SEL to display its value (default 00);

press to select the desired value (from 01 to 199);

press

SEL to confirm the new value and display again the H3

code;

press PRG to memorize the access code and exit the

procedure.

REMOVING THE CODE

repeat the operations described above and give the H3 parameter

the value 00 (H3=00). In this way you can program your
controller/s without selecting the access code.

WHAT TO DO IF THE REMOTE CONTROL DOESN'T WORK

check that the remote control is equipped with batteries aligned

correctly;

replace spent or weak batteries;

check that there are no obstacles between controller and

transmitter;

periodically clean the transmitter and the controller with a soft cloth;

remember that the remote control's usable range is within 3 meters

away from the controller.

in case parameters are accessible but the user is not allowed to

change values, verify "H2" parameter (refer to the USER manual)


MODELS
There are several versions available, in different languages:

Language Type

Order

Nr.

English

EC2- IRE

804 345

German

EC2- IRD

804 346

French

EC2- IRF

804 347

Spanish

EC2- IRS

804 348

Italian

EC2- IRI

804 349

Emerson Electric GmbH & Co.OHG is not to be held responsible for erroneous
literature regarding capacities, dimensions, applications, etc. stated herein.
Products, specifications and data in this literature are subject to change without
notice. The information given herein is based on technical data and tests which
ALCO CONTROLS believes to be reliable and which are in compliance with
technical knowledge of today. It is intended only for use by persons having the

appropriate technical knowledge and skills, at their own discretion and risk. Since
conditions of use are outside of ALCO'S control we cannot assume any liability for
results obtained or damages occurred due to improper application.

This document replaces all former versions.