Jøtul f 500 woodstove clearances, Usa/canada – Jotul F 500 Benutzerhandbuch
Seite 16

16
USA/CANADA
Stove clearances
Unprotected surface
Protected surface NFPA 211
Parallel installation
Parallel installation
Side
Rear
Corner*
Side
Rear
Corner*
Stove- no heatshields
14" A
18" B
13" C
6" D
12" E
9" F
Single wall pipe
355mm
460mm
330mm
150mm
300mm
230mm
Stove with rear heatshield
14" G
10" H
9" I
6" J
10" K
9" L
Single wall pipe
355mm
255mm
230mm
150mm
255mm
230mm
Stove with rear heatshield
14" M
6" N
9" O
6" P
6" Q
6" R
With connector shield
355mm
150mm
230mm
150mm
150mm
150mm
Stove with rear heatshield
14" S
6" T
9" U
6" V
6" W
6" X
With double wall pipe
355mm
150-mm
230mm
150mm
150mm
150mm
Connector
Unprotected surface
Protected surface NFPA 211
clearances (pipe)
Vertical installation
Vertical installation
Single wall pipe
18"
12"
460mm
300mm
Single wall pipe
6"
6"
with connector shields
150mm
150mm
Double wall pipe
6"
6"
150mm
150mm
Connector
Unprotected surface
Protected surface NFPA 211
clearances (pipe)
Horizontal installation
Horizontal installation
Single wall connector
18" 460mm
12" 300mm
Double wall pipe
6" 150mm
6" 150mm
Mantel and trim
Stove to 1" thick or less, side trim
12" 300mm
clearances
Stove to 1" thick or less, top trim
16" 410mm
Stove to mantel- maximum mantel depth 12"
30" 765mm
* Attention: Stove and pipe clearances must both be taken into
Consideration. The greater clearance dictates the stove’s position.
* Use of the right side load door is prohibited in alcove and
Corner installations.
Jøtul F 500 Woodstove Clearances