Change of function of DIP switch 8 and actions for customers

Identity-Number: 805038

page 6 of 8

Table 2: Overview of firmware functions

PROFIBUS-bus

terminal

till serial

number 37343

PROFIBUS-bus terminal

as of serial number 37344

PROFIBUS

DP/V0-Mode

DP/V1-Mode

Device entry

Typ 8644

Typ 8644

8644-DP

(DIP8=OFF)

ME02

8644-DPV1

(DIP8=ON) ME02

Name of GSD-file

BUER00F0.gsd

BUER00F0.gsd BUV100F0.gsd

BUER06BA.gsd

Old and new version of PROFIBUS-bus

terminal can be replaced

X

X

X

--

DP/V0 support

(cyclic communication)

184 byte for

process data,

maximum

184 byte of

process data,

maximum

184 byte for

process data,

maximum

176 byte of

process date,

maximum

PCP module operation

--

--

X

X

DP/V1 Read an DP/V1 Write support (acyclic

communication), Class 1 and Class 2 masters

--

--

--

X

Communication with PCP modules via „normal“

process data (DP/V0)

--

--

X

X

Parameterisation of several I/O´s via dialog

boxes in the configuration tool

--

--

--

X

Specification of safety values using the

configuration tool

--

--

--

X

Byte rotation for IB IL 24 DI 16 and IB IL 24 DO

16 for adaptation to the control system format

--

--

X

X

Byte rotation for IB IL 24 DI32 and IB IL 24 DO

32

--

--

New in

firmware B or

later

New in firmware

B or later

Acknowledgement of bus stops, either

automatically or via the application program

--

--

X

X

Acknowledgement at I/O errors, either

automatically or via the application program

--

--

X

X

Diagnostics in PROFIBUS-bus terminal

X

X

X

X

Diagnostics in identification format

--

--

--

X

Diagnostics as status PDU

--

--

--

X

Stop response can be set via DIP switches

X

--

--

--

Stop response can be set via parameter

telegram

--

--

X

(cp.