KROHNE DK 32-DK 34 Reed L Ex II2G DE Benutzerhandbuch
Seite 2

07/2009
MA DK-Reed-L-Ex-II2G-AD-R02-de-en
4000408202
Reed Contact unit to mount on DK32 / DK34
Manual
Electrical equipment for explosive hazardous areas
Equipment Category
II 2 G to use in explosive hazardous areas zone 1
Declaration of Conformity
The electrical equipment operates as a simple device. It is in
conformity with intrinsic safety EN 60079-11:2007, para. 5.7
Ex- Marking
none (because it isn’t required in accordance to 60079-11, para. 5.7)
Reed-contact type
Bistable contact with an intal tension magnet
Operating temperature range
-20°C to +120°C
-20°C to +200°C (HT- design)
Isolation
500 Vac to Earth
Electrical data
Only for connection on certified intrinsically safe circuits,
Maximum values:
Ui = 30 V
Ii = 100 mA
Ci negligible
Li negligible
Temperature class
T6, maximum operating temperature 40°C
T5, maximum operating temperature 55°C
T4, maximum operating temperature 90°C
T3, maximum operating temperature 155°C
T2, maximum operating temperature 200°C
Electrical connection
FEP coated connection cable
Terminal
assignment
br = brown
bl
=
blue
rt = red
General
Install and operate the device in accordance with the operating instruction
Installation,
Starting
Requirements
Statutes, recommendation, engineering standards for application have to be
kept. The warrant of intrinsic safety is only by interconnection with
intrinsically safe equipment.
To prevent risk of flammable hazard in case of malfunctions and or transient
in system with equipotential bonding system, use galvanic separation for
(connected) supplying or switching equipment.
Maintenance, Service
No modifications on equipment in explosive hazardous areas are permitted.
rt
bl