Can port, Cable fixing and strain relief, Installation – Lenze EL 103 ECO PLC Benutzerhandbuch
Seite 30

Installation
Electrical installation
LDCDS−EL100EMA DE/EN 3.2
30
l
H1inst−Kabelfix_EL103_B
CAN port
)
Note!
ƒ
Only connect terminals of the same signal type.
ƒ
For further information with regard to the CAN bus system please refer to
the CAN Communication Manual.
We recommend the use of CAN cables according to ISO 11898−2.
Description
Connection type
Cable type
CAN bus connection
Pin 1: CAN−GND (CG)
Pin 2: CAN−LOW (LO)
Pin 3: CAN−SHIELD
Pin 4: CAN−HIGH (HI)
Pin 5: Not assigned
5−pole Phoenix
Combicon socket
CAN cable acc. to
ISO 11898−2 with
Phoenix Combicon
plug, MSTB 2.5 /
5−STF−5.08
EL100−011
CAN cable shield connection
via cable clamp on the back of the device:
EL100−033
Cable fixing and strain relief
Fix the cable bundles on the back of the EL 103 using cable ties.
EL100−034