Technical data, 4technical data – Lenze MC−ISI Benutzerhandbuch
Seite 28

4
Technical data
MA_MCISI DE/EN 3.0
28
l
H1_Daten−Kommunikation_MC−ISI
4
Technical data
MC−ISI
Conformity, approval, directive
Conformity
CE
EN 61000−6−4
EN 61000−6−2
EMC Directive Class A,
industrial premises
Approval
UR
UL 508
CSA C22.2
Process Control Equipment
(File−No. E236341)
Directive
RoHS
−
Products lead−free in accordance with
CE Directive 2011/65/EU
General data and operating conditions
See standard device
Electrical data
Current
< 0.2 A
at standard device supply voltage of
24 V
Electrical isolation to the
fieldbus
yes
Mechanical data
Mass
< 0.1 kg
Communication
Type
Serial interface
COM A
Type
RS232, electrically isolated
Isolation
2.500 Vrms
ESD protection
15 kV
COM B
Type
RS422/485 (switchable)
Isolation
2.500 Vrms
ESD protection
15 kV
Baud rate
600 Baud ... 115.2 kBaud
Data frame
5, 6, 7, 8 and 9 Bit
Parity
Even, odd, none, space & mark