21

Connection:

•

Connect the setpoint potentiometer (10 k

Ω

lin.

) to the terminals

42, 43, 44 or the selected master-voltage to the terminals 43(+)
and 44(-) of the 2003 board.

•

Connect terminal 41 to terminal 8 of the 470 / 480 controller.

•

When using the setpoint potentiometer provided, the mechanical
screw joint must be provided with an additional PE connection
and the connections must be insulated or covered.

•

Set the trimmer "V

master - coarse

" to the right stop.

•

Reinstall the protection cover. (Use the original plastic cover for
470 controllers!

3.2

Terminal-connection diagram

The terminal-connection diagram shows the wiring between the
2003 option board with setpoint potentiometer and the 470 / 480
controller.

A

S

E

Setpoint potentiometer

10 K lin

470 / 480

2003

7

8

9

41

42

43

44

Remove the setpoint-potentiometer connection from the terminals
7, 8, 9 of the basic instrument and connect them to the 2003 option
board!