Electrical installation – Lenze ELCAFHIxxx4D34NNPM Highline Benutzerhandbuch
Seite 76

Electrical installation
Control terminals
l
76
EDKLCFH3024−XPM DE/EN 6.0
Digital outputs
)
Note!
ƒ
Delay time between triggering and switching of the digital outputs: approx.
100 ms.
ƒ
If inductive loads are being connected, it is essential to use a spark
suppressor at the digital output.
X45 − Digital outputs DO1, DO2
Pin
Signal
Description
Data
Connector: female, 4−pin, M12
1
n. c.
Not assigned
2
Signal 2
DO2
HIGH
U
DC
at X11
3
Gnd
Reference potential
LOW
0 ... +4 V
4
Signal 1
DO1
Max. 500 mA per output
X46 − Digital outputs DO3, DO4
Pin
Signal
Description
Data
Connector: female, 4−pin, M12
1
n. c.
Not assigned
2
Signal 2
DO4
HIGH
U
DC
at X11
3
Gnd
Reference potential
LOW
0 ... +4 V
4
Signal 1
DO3
Max. 500 mA per output
Analog inputs, analog outputs
X51 − Analog inputs AI1, AI2
Pin
Signal
Description
Data
Connector: male, 4−pin, M12
1
AI1+
Analog input 1
2
AI1−
Analog input 1
3
AI2+
Analog input 2
4
AI2−
X52 − Analog outputs AO1, AO2
Pin
Signal
Description
Data
Connector: male, 4−pin, M12
1
AO1
Analog output 1
2
AO2
Analog output 2
3
GND
Reference potential
4
GND
Diagnostic interface
X70 − Diagnostic interface
Pin
Signal
Description
Data
1 ... 10
Connection of keypad or diagnostic
adapter
Connector: female, RJ69