DPA/DCV

•Operation

General

The DPA/DCV allows you to set two independent trip points on a DC

voltage signal (typically 0-5 V). The alarm outputs are dual SPDT relay
contacts.

Setup

The alarm relay coils operate according to each setpoint/deadband

configured via front panel multiturn potentiometers. Internal push
fit jumpers determine the alarm type (high or low acting) and coil
energisation (normally energised/de-energised).

DPA/DCV block diagram.

DC Volts

Alarm 1

Power

Supply

Alarm 2

24 V DC (Out)