Calibrationandsetup – Weidmuller DPADRT - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 20

Advertising
background image

0

•CalibrationandSetup

General

The SET (setpoint) and DB (deadband) adjustments control the

setpoint and hysteresis for each alarm channel. Internal jumpers
control the alarm type and relay coil energisation.

Equipmentrequirements
• Two accurate decade resistance boxes. Note set Resistance box 

to the minimum value of R. Resistance box one is adjusted to give
the required difference signal.

• Flat bladed screwdriver (blade width less than .4 mm / 0.1 inch)
Note 1: Resistance box  can be replaced by an accurate resistor
equal to the minimum amount of R (the smaller resistor).

Terminalconnectionsforcalibration

Signaltype

Terminal

Input signal

Common

2

Resistance Box 2

3

Resistance Box 1

4

Power supply

Neutral (−)

9

Live (+)

10

Setpoint(SETControl)adjustment
The SET controls for each channel are on the front panel of the
transmitter. For both high and low type alarms you turn the control
clockwise to trip the alarm and anticlockwise to reset it. The procedure
for adjustment is as follows:

1. Connect up the instrument according to the table above.
. Set the inputs to the trip point.
. Turn the SET control anti-clockwise until the LED extinguishes.
4. Slowly turn the SET control clockwise until the LED lights up.