Deadband(DBControl)adjustment

The deadband control adjusts the point at which a tripped alarm

resets. This point will be above the setpoint for a low type alarm or
below for a high type. The procedure for adjusting the DB control is as
follows:

1. Adjust the SET control
. Set the deadband to maximum by turning the DB control fully

clockwise.

3. Trigger the alarm by setting the input signal to ‘full scale’ (for a high

type alarm) or ‘zero’ (for a low type alarm).

4. Set the input to the level at which the alarm should reset.
. Decrease the deadband (turn control anticlockwise) until the LED

extinguishes.

6. Check that the setpoint and deadband are set correctly.

Internalsettings(Alarmtypeandcoilenergisation)

To change the alarm type or coil energisation:
1. Remove the left hand side plate.
. Set the links according to the diagram (right).
3. Replace the side plate.