Weidmuller DPARTD - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 21

Advertising
background image

1

14

7

VR1

. . . . . . . .

1. Adjust the SET control
. Set the deadband to maximum by turning the DB control fully

clockwise.

. Trigger the alarm by setting the input signal to ‘full scale’ (for a high

type alarm) or ‘zero’ (for a low type alarm).

4. Set the input to the level at which the alarm should reset.
. Decrease the deadband (turn control anticlockwise) until the LED

extinguishes.

6. Check that the setpoint and deadband are set correctly.

Internalsettings(Alarmtypeandcoilenergisation)

To change the alarm type or coil energisation:
1. Remove the left hand side plate.
. Set the links according to the diagram (right).
. Replace the side plate.

LeadLengthCompensationAdjustment(factorysetting)

Note: you will require an accurate 100 Ω resistor (in addition to the

requirements above). The procedure for adjusting this control is:

1. Remove the electronics from the housing.
. Connect up the alarm according to the

table above.

. Connect the 100 Ω resistor between

terminal 4 and the simulator Bsense
connection.

4. Set the RTD simulator to 0 °C.
. Adjust VR1 on the personality card until

the voltage across terminals  and  of
the instrument is twice that across the
resistor.

This completes the adjustment.