Deadband(DBControl)adjustment

The deadband control adjusts the point at which a tripped alarm resets.

This point will be above the setpoint for a low type alarm or below for a
high type. The procedure for adjusting the DB control is as follows:

1. Adjust the SET control
. Set the deadband to maximum by turning the DB control fully

clockwise.

. Trigger the alarm by setting the input signal to ‘full scale’ (for a high

type alarm) or ‘zero’ (for a low type alarm).

4. Set the input to the level at which the alarm should reset.
. Decrease the deadband (turn control anticlockwise) until the LED

extinguishes.

6. Check that the setpoint and deadband are set correctly.

Internalsettings(Alarmtypeandcoilenergisation)

To change the alarm type or coil energisation:
1. Remove the left hand side plate.
. Set the links according to the diagram (right).
. Replace the side plate.

CJCTrackingAdjustment(factorysetting)

The procedure for CJC tracking adjustment

is as follows:

1. Remove the electronics from the housing.
. Connect up the alarm according to the

table above.

. Set the thermocouple simulator to  % below the lowest

temperature in the range of the instrument, e.g., for a 0-400 °C
span, set the simulator to -8 °C.

4. Adjust VR1 on the personality card until the voltage between pins 8

and  of the personality card is 0.00 mV.

This completes the CJC tracking adjustment.

14

7

.

. . . . .

8

9

VR1