Calibration – Weidmuller TWI-1 - Signal isolator in 2-wire design, 1-channel Benutzerhandbuch

Seite 12

Advertising
background image

1

•Calibration

general

All instruments are fully calibrated before leaving the factory and

should not need adjustment until the next scheduled calibration.

equipmentrequirements
• A suitable signal source (mA or V) for the inputs
• Two accurate digital multimeters (accurate to 0.05 mV and ±0.1 μA)
• A suitable regulated power supply, e.g., RPS/40 V AC/4 V DC/x
• Flat bladed screwdriver (blade width less than .54 mm/0.1 inch)

Digital multimeters are frequently better at measuring voltages than

currents, so you may wish to measure the voltage across an accurate
standard resistor (say 10 Ω ±0.05 %) when monitoring current signals.

If you have a Mann Industries Portacal 1000 calibrator you will not

need the second multimeter or the regulated power supply.

Terminalconnectionsforcalibration

ModelNumber

Cat.No.

Channel

Signal

Signaltype

Terminal

TWI-1/4-20 mA 7940010159

One

4-20 mA input

DC milliamp source +

1

DC milliamp source −

3

4-20 mA output

mA output +

4

mA output −

6

TWI-1/0-10 V

7940011660

One

0-10 V input

DC Voltage source +

1

DC Voltage source −

3

4-20 mA output

mA output +

4

mA output −

6

Note: check all connection details against the instrument top label.