42

17.7.3 Making the load connections

17.7.4 Rear panel description

Fig. 17-1: FPS-T1U Rear panel

The load wires should be properly terminated with terminals securely attached. DO NOT use unterminated
wires for load connection at the FPS-T1U.

Hazardous voltages may exist at the outputs and the load connections
when using a power supply with a rated output greater than 40V. To
protect personnel against accidental contact with hazardous voltages,
ensure that the load and it's connections has no accessible live parts.
Ensure that the load wiring insulation rating is greater than or equal to
the maximum output voltage of the power supply.

WARNING

!

1

2

3

5

1

1. Mounting brackets. Use M6x12 screws to fix the FPS-T1U to the rack.
2. Output voltage terminals rugged busbars. Use M5x12 screws for load wires recommended
Tightening torque 24~31 Kgf.cm.
3. Micro-Fit 3.0

TM

Dual Row Right Angle 16pins (Molex) connector for control and monitoring signals.

4. Ground stud M4 (three place).
5. IEC320 AC inlet ,shown for FPS-T1U. For FPS-T1U/P there are no IEC320 inlets on the rack.