Fig 19-4 shows typical output voltage trimming connection for FPS1000 unit ‘A’ inside the rack
Units ‘B’ and ‘C’ connections - Refer to 17.7.5

Signals are accessible at the J1(A), J2(B), J3(C) connectors on the rear panel of the rack
Fig 19-5 shows typical connection for FPS1000 unit ‘A’. inside the rack
Units ‘B’ and ‘C’. connections - Refer to 17.7.5

Note: AC_FAIL, DC_OK and TEMP.ALARM are open collector signals

Application

Monitoring

and Control

circuits

FPS-1000 Module B

FPS-1000 Module C

FPS-T1U

FPS1000
Module A

12V AUX

AC_FAIL_A

DC_OK_A

TEMP.ALARM_A

SIGNAL RET

10K

10K

10K

3

14

5

11

9

J1(A)

J2(B)

J3(C)

19.3 Output Voltag Trimming

FPS-1000 Module B

FPS-1000 Module C

FPS-T1U

FPS1000
Module A

J1(A)-8

J1(A)

J2(B)

J3(C)

J1(A)-6

J1(A)-7

R1

R2

R1&R2:0.5W

+S

-S

V_TRIM

FPS1000-24:
R2=0.0785*V

2

out

-5.819*V

out

+105.132

R1(K

Ω)=20(KΩ)-R2(KΩ)

FPS1000-48:
R2=0.0497*V

2

out

-7.2795*V

out

+259.04

R1(K

Ω)=50(KΩ)-R2(KΩ)

FPS1000-32:
R2=0.0463*V

2

out

-4.5805*V

out

+109.49

R1(K

Ω)=20(KΩ)-R2(KΩ

Ω)

FPS1000-12:
R2=0.0324*V

2

out

-1.1298*V

out

+9.9342

R1(K

Ω)=5(KΩ)-R2(KΩ)

19.4 Supervisory Signals

19.5 Grounding outputs
Either the positive or negative output terminals can be grounded. To avoid noise problems caused by
common-mode current flowing from the load to ground, it is recommended to ground the output terminal
as close as possible to the power supply's output. Always use two wires to connect the load to the power
supply regardless of how the system is grounded.

Fig 19-5 Supervisory Signals