generation, material cones and echoes from the

vessel wall (with solids). To adapt the sensor to

these different conditions, you should first select

"Liquid" or "Solid".

Medium

Liquid

With solids, you can also choose between "Pow-

der/Dust", "Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is

adapted perfectly to the product and measurement

reliability, particularly in products with bad reflective

properties, is considerably increased.
Enter the requested parameter via the appropriate

keys, save your settings and jump to the next menu

item with the [->] key.

Vessel form

Apart from the medium, the vessel shape can also

influence the measurement. To adapt the sensor to

these measuring conditions, this menu item offers

different options depending on whether liquid or

solid is selected. With "Liquid" these are "Storage

tank", "Stilling tube", "Open vessel" or "Stirred

vessel", with "Solid", "Silo" or "Bunker".

Vessel form

Storage tank

Enter the requested parameter via the appropriate

keys, save your settings and jump to the next menu

item with the [->] key.

Damping

To suppress fluctuations in the measured value

display, e.g. caused by an agitated product sur-

face, an integration time can be set. This time can

be between 0 and 999 seconds. Keep in mind that

the reaction time of the entire measurement will

then be longer and the sensor will react to

measured value changes with a delay. In general, a

period of a few seconds is sufficient to smooth the

measured value display.

Damping

0 s

Enter the requested parameter via the appropriate

keys, save your settings and jump to the next menu

item with the [->] key.

Linearisation curve

A linearization is necessary for all vessels in which

the vessel volume does not increase linearly with

the level - e.g. with a cylindrical or spherical tank -

and the indication or output of the volume is

required. Corresponding linearization curves are

preprogrammed for these vessels. They represent

the correlation between the level percentage and

vessel volume. By activating the appropriate curve,

the volume percentage of the vessel is displayed

correctly. If the volume should not be displayed in

percent but e.g. in l or kg, a scaling can be also set

in the menu item "Display".

Linearisation curve

linear

Enter the requested parameter via the appropriate

keys, save your settings and jump to the next menu

item with the [->] key.

Sensor-TAG

In this menu item, a clear identification can be

assigned to the sensor, e.g. the measurement loop

name or the tank or product name.

Sensor-TAG

Sensor

With this menu item, the Basic adjustment is

finished and you can now jump to the main menu

with the [ESC] key.

Gating out of false signals

High sockets or vessel installations, such as e.g.

struts or agitators as well as buildup and weld joints

on the vessel walls cause interfering reflections

which can impair the measurement. A false echo

30

VEGASON S 62

Set up with the indicating and adjustment module