Assign unit number, Set number of floats, Set baud rate – VEGA VEGAFLEX 81 Modbus and Levelmaster protocol Coax probe Benutzerhandbuch

Seite 82

Advertising
background image

82

11 Anhang

VEGAFLEX 81 • Modbus- und Levelmaster-Protokoll

42283-DE-130311

Response:

Parameter

Length

Code/Data

Report Level (and Temperature)

6 characters ASCII

UuuNnn

Assign Unit Number

Request:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNnn

Response:

Parameter

Length

Code/Data

Assign Unit Number

6 characters ASCII

UuuNOK
uu = new Address

Set number of Floats

Request:

Parameter

Length

Code/Data

Set number of Floats

5 characters ASCII

UuuFn

Response:

Parameter

Length

Code/Data

Set number of Floats

6 characters ASCII

UuuFOK

Wird die Anzahl auf 0 gesetzt, wird kein Füllstand mehr zurückgemeldet

Set Baud Rate

Request:

Parameter

Length

Code/Data

Set Baud Rate

8 (12) characters ASCII

UuuBbbbb[b][pds]
Bbbbb[b] = 1200, 9600 (default)
pds = parity, data length, stop bit

(optional)
parity: none = 81, even = 71 (de-

fault), odd = 71

Response:

Parameter

Length

Code/Data

Set Baud Rate

11 characters ASCII

Beispiel: U01B9600E71
Gerät an Adresse 1 ändern zu Baudrate 9600, Parität even, 7 Datenbits, 1 Stoppbit

Advertising