Burkert Type 8633 Benutzerhandbuch

Seite 6

Advertising
background image

ELECTRICAL CONNECTION WITH ASI BUS

Control functions

FLUIDIC / PNEUMATIC CONNECTION

ELECTRICAL CONNECTION WITHOUT ASI BUS

ston rod

ds to

along the

mm

to the
aperture

eal on the

head

ctuator with

ormed

Configuration

LED green
Control valve(s) operated

LED green
Power supply for
initiators

LED yellow Initiator 1

(upper) triggered

LED yellow Initiator 2

(lower) triggered

Terminal Inductive proximity switch

1)

Mechanical limit switch

2)

1

Supply to initiators + 24 V

Supply to limit switches + 24 V

2

Supply to inititators GND

Supply to limit switches GND

3

Binary output initiator 1 (NO)

Output limit switch 1 (NO)

4

not connected

Output limit switch 1 (NC)

5

Reference for inititator 1 GND

Reference for limit switch 1 GND

6

Binary output initiator 2 (NO)

Output limit switch 2 (NO)

7

not connected

Output limit switch 2 (NC)

8

Reference for initiator 2 GND

Reference for limit switch 2 GND

9

Valve actuation 0 V/ 24 V

10

Valve actuation GND

24 V version

110 V or 230 V version

Terminal Mechanical limit switch

1

Supply to limit switches

2

Supply to limit switches

3

Output limit switch 1 (NO)

4

Output limit switch 1 (NC)

5

Output common pole

6

Output limit switch 2 (NO)

7

Output limit switch 2 (NC)

8

Valve actuation N

9

Valve actuation L 1

10

Valve actuation N

Bus drive via AS interface

LED yellow
Valve supplied with current

LED green
ASI bus status display LED 1
LED red
ASI bus status display LED 2

LED yellow

Initiator 1 (upper)
triggered

LED yellow

Initiator 2 (lower)
triggered

M12 circular plug
connector

Status display
ASI bus

Data bit

D3

D2

D1

D0

Signal

Input
Initiator 1

Input
Initiator 2

not con-

nected

Output control valve(s)

Value 0

Position not reached

Control valve(s) off

Value 1

Position reached

Control valve(s) on

Parameter bit P3

P2

P1

P0

Signal

not connected

Watchdog

Value 0

Watchdog

deactivated

Value 1

Watchdog

activated

1/P

2/A

1

2/A

2

3/R

Exhaust air

1) For supplying the initiators, the voltage must have < 10% residual ripple
2) AC or industrial DC

GB

GB

GB

GB

LED 1 (green) LED 2 (red)

Status signalled

off

off

POWER OFF

on

off

ok

flashes

on

Slave adress = 00

Pin 1: Bus +
Pin 3: Bus -

3

1

2

4

bit configuration

standard Device

Device for A/B-Slave addressing

Certification:

Approval no. 31902 (to V.2.1) none

Programming data:

E/A-configuration

B hex (1 output, 2 inputs

ID-Code

F hex (see under for pin
configuration)

A hex (see under for pin
configuration)

ext. ID-Code 1

F hex

7 hex

ext. ID-Code 2

F hex

E hex

Profil

S-B.F.F

S-B.A.E

Control fucntion

Pneumatic connection of
MiniTOP to valve

Output
MiniTOP

Input process valve

A

Process valve
closed by spring

force in rest position

2/A

1

(port

2/A

2

not

present)

Lower actuator chamber

B

Process valve open
by spring force in
rest position

2/A

1

(port

2/A

2

not

present)

Upper actuator chamber

I

Process valve
closed in rest
position

2/A

1

2/A

2

Lower actuator chamber
Upper actuator chamber

Process valve open
in rest position

2/A

2

2/A

1

Lower actuator chamber
Upper actuator chamber

Advertising