Specials of dip switch 8 – Burkert Type 8644 Benutzerhandbuch

Seite 7

Advertising
background image

ENGLISH

Change of function of DIP switch 8 and actions for customers

Identity-Number: 805038

page 7 of 8

PROFIBUS-bus

terminal till

serial number

37343

PROFIBUS-bus terminal

as of serial number 37344

PROFIBUS

DP/V0-Mode

DP/V1-Mode

Device entry

Typ 8644

Typ 8644

8644-DP

(DIP8=OFF)

ME02

8644-DPV1

(DIP8=ON) ME02

Name of GSD-file

BUER00F0.gsd

BUER00F0.gsd BUV100F0.gsd

BUER06BA.gsd

Invoke ID transmission

(e.g. for IB IL POS 200)

--

--

New in

firmware B or

later

New in firmware

B or later

dynamic configuration

(I/O´s reserved in the PLC, e.g. for easy

expansion)

--

--

--

New in firmware

B or later

Freely assignable station ID (2 byte) for

improved identification in the network

--

--

--

New in firmware

B or later

Specification of failsafe values using the

configuration tool

--

--

--

X

Failsafe values even without connection to the

PLC

--

--

--

New in firmware

B or later

Improved I/O diagnostics during startup

--

--

--

New in firmware

B or later

Configuration can be stored (additional

verification using the latest valid configuration)

--

--

--

New in firmware

B or later

Specials of DIP switch 8:

In difference to PROFIBUS-bus terminal till serial number 37343 (GSD-file: BUER00F0.gsd, device entry: „Typ
8644“) the new devices as of serial number 37344 don’t use DIP switch 8 for adjustment of Stop behaviour.
They use it to distinguish between DP/V0- an DP/V1-mode. In new devices you can adjust Stop behaviour via
parameter telegram, cp. Figure 2.

In delivery of new devices as of serial number 37344 DIP switch 8 is in position „OFF“. So the device can
replace parent devices till serial number 37343 and has additionally several new functions. But these new
functions can only be used in new devices as of serial number 37344. For this case use GSD-file BUV100F0.gsd
with device entry „8644-DP (DIP8=OFF) ME02“.
If those new functions are not needed and DIP switch 8 is „OFF“, you can also use the GSD-File for devices till
serial number 37343 (GSD-file: BUER00F0.gsd, device entry: „Typ 8644“). But in this case there is no possibility
to adjust Stop response (cp. Table 2).

If DIP switch 8 is set to „ON“, the new device as of serial number 37344 offers some further functions which you
can find in Table 2. For this case use GSD-file BUER06BA.gsd with device entry „8644-DPV1 (DIP8=ON)
ME02“.