Connection configuration of the flow
type 8623-2

M12, 4-pole
supply voltage
and standard
signal input
external setpoint

Changing the cable outlet direction

Fig.:

Changing the cable out

➔ Unscrew the 4 screw

the controller and re
carefully

➔ Remove the screw t

remove the plastic c

➔ Detach the plate fro

➔ Pull out the cube do

replace in the desire

➔ Place the plate onto

(the pins must enga
guides.)

➔ Lay on the plastic cr

the screw through th

➔ Connect the controll

proportional valve.

Interference with the device is only allowed by specialist
personnel using suitable tools! Before interfering with the

controller, always switch off the voltage!

Connecting to the proportional valve

Fig.: Connecting the controller to the

proportional valve

➔ Unscrew the 4 screws on the front panel of themcontroller and

remove the cover carefully.

➔ Place the housing of the controller with the seal onto the valve.

➔ Screw the required controller tightly to the valve.

On screwing the controller onto the proportional valve,
make sure the seal is correctly seated!

➔ Place the cover on the controller and screw it tight with the

4 screws.

Make sure the cover is placed on the right way round
(pinned strips must engage in the sockets.)

Technical data 8625-2

Inputs
Sensor input

PT 100

Temperatur range

-50 °C ... +150 °C / -58 °F ... 302 °F

Resolution

0.25 °C or 0.45 °F

1)

Precision

1.5 °C or 2.7 °F

1)

1 setpoint input

4 - 20 mA / 0 - 10 V adjustable
Resolution

10 bit

Input impedance

(4 - 20 mA) < 200

Input impedance

(0 - 10 V)

> 300 k

Controller
Control algorithm

PI - control

Scan time T

A

50 ms

Amplification factor K

P

0.00 - 10.00 %/K

Reset time T

N

0.1 - 200.1 s

Scaling

- 50 °C ... +150 °C or -58 °F ... 302 °F

Order no.

143571

1)

Calibrated to 1 m conductor length and 0.5 mm

2

conductor

cross-section.

Technical data 8624-2

Inputs
Sensor input

4 - 20 mA / 0 - 10 V adjustable
Resolution

10 Bit

Input impedance

(4 - 20 mA) < 200

Input impedance

(0 - 10 V)

> 300 k

1 setpoint input

4 - 20 mA / 0 - 10 V adjustable
Resolution

10 Bit

Input impedance

(4 - 20 mA) < 200

Input impedance

(0 - 10 V)

> 300 k

Controller
Control algorithm

PI - control

Scan time T

A

27 ms

Amplification factor K

P

0.00 - 10.00

Reset time T

N

0.5 - 200.1 s

Scaling

0.000 - 9999

Order no.

143570

Technical data 8623-2

General technical data
for controllers 8623-2, 8624-2 and 8625-2

Operating voltage

24 V DC

Power consumption

max. 0.3 W (without proportional valve)

Output current

max. 1.0 A

(to valve)
Operating temperature

-10 ... +60 °C / 14 °F ... 140 °F

Interference resistance

to EN 50082-2

Interference emmission

to EN 50081-2

Output
PWM output

24 V - pulse width modulated

Housing
Cable outlet

rotatable in 90° steps

System of protection

IP 65

Material

polyamide

Dimension (B x H x T)

54 x 54 x 61 mm

Inputs
Sensor input

2 frequency inputs, 2 - 1000 Hz

Precision

± 1 %

Signal types

sine, square, triangle (

300 mV

ss

)

1 setpoint input

4 - 20 mA / 0 - 10 V adjustable
Resolution

10 Bit

Input impedance

(4 - 20 mA) < 200

Input impedance

(0 - 10 V)

> 300 k

Controller
Control algorithm

PI - control

Scan time T

A

45 ms

Amplification factor K

P

0.00 - 10.00 ‰/Hz

Reset time T

N

0.1 - 200.1 s

K-factors 1 and 2

0.0 - 6552

Ratio

0.00 - 10.00

Scaling

0.00 - 655.2

Filter

software filter with PT1 behaviour
time constant = 8*T

A

Order no.

143569

reas and function

niature controllers, in combination with

ves, serves to control

piping

(Flow rate controller 8623-2)

uids and

(Pressure controller 8624-2)

ature of

(Temperature controller 8625-2)

oportional valves
023, 6223, 2832, 2834

adjustable PI control behaviour

ion on the valve, thanks to compact design of

n of a proportional valve

fication via standard signal 4-20 mA / 0-10 V

of flow rate by means of a flow rate sensor with

put (frequency proportional to flow rate)

ensors with frequency output of max. 1000 Hz

ontrol

of the pressure by means of a pressure

h standard output signal

of the temperature by means of a PT 100 sensor

ng

TECHNICAL DATA

TECHNICAL DATA

INSTALLATION / COMMISSIONING

INSTALLATION / COMMISSIONING

t to make technical changes without notice.