Burkert Type 8709 Benutzerhandbuch

Seite 10

Advertising
background image

36

Pin assignment of field bus LFC Types 8718, 8719 and
LFM Types 8708, 8709

PROFIBUS DP
Socket M12, B-coded
(DP V1 max. 12 Mbaud)

Pin Configuration

4

2

3

5

1

1

VDD

2

R x D / T x D – N
(A cable)

3

DGND

4

R x D / T x D – N
(B cable)

5

or used

DeviceNet or CANopen
M12 plug

Pin Configuration

4

2

3

5

1

1

Shielding

2

not used

3

DGND

4

CAN_H

5

CAN_L

english

37

oPeraTion and funcTion

9.

safety instructions

9.1.

Warning!

Risk of injury from improper operation!
Improper operation may result in injuries as well as
damage to the device and the area around it.

The operating personnel must know and have under-

stood the contents of the operating instructions.
Observe the safety instructions and intended use.

Only adequately trained personnel may operate the

equipment/the device.

operation of the lfc / lfm

9.2.

The LFC / LFM is operated by means of analogue standard
signals or field bus communication as well as binary inputs.
For operating and status displays 3 or 4 LEDs are also
used as binary outputs.
There is also a serial interface (RS232) via which a con-
nection to a PC can be established, e.g. using the “Mass
Flow Communicator” software.

english

38

Selecting the standard signals / Assigning

the binary inputs

The required configuration of the standard signal
type as well as the assignment of the binary inputs
can be specified on order placement or can be
configured via the “Mass Flow Communicator”
software (see also Chapter

11.1. Mass Flow Com-

municator (PC software).

LED assignment / Assigning binary outputs


The LED assignment (except the Power and the
Error LED) as well as the assignment of the binary
outputs can also be configured via the “Mass Flow
Communicator” PC software (see also Chapter
11.1. Mass Flow Communicator (PC software).

english

39

leds

9.2.1.

3 or 4 LEDs are used for operating and status displays.

Standard assignment of the LEDs:
LED status

Description

Power
(green)

lit

The device is connected to the
power supply.

flashing Autotune function is active.

Commu-
nication
(yellow

5)

)

lit

The device communicates via the
field bus or the serial interface
(RS232).

Limit (y)
(blue

6)

)

lit

LFC:
Indicates that the actuating variable
of the proportional valve has almost
reached 100%. In practice this
usually means that the pressure on
the controller is not adequate to
reach the required flow-rate.
LFM:
Indicates that the actual value
has almost reached the nominal
flow-rate.

flashing The device is in an operating state

other than controlled operation or
the Autotune function.

english

Type 8708, 8709, 8718, 8719

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: