PULS UZK12.071 Benutzerhandbuch

Seite 3

Advertising
background image

UZK12: Battery Module Instruction Manual
UZK12: Bedienungsanleitung für Batteriemodule

Technical Data

1)

Technische

Daten

1)

UZK12.071

UZO12.07

2)

UZK12.261

UZO12.26

2)

Battery Type

Batterietyp

nom.

VRLA (lead acid)

VRLA (lead acid)

Battery Design Life

Ausgelegte Batterielebensdauer

acc EUROBAT

3 to 5 years

10 to 12 years

Voltage of Battery Module

Spannung des Batteriemoduls

nom.

DC 12V

DC 12V

Battery Capacity

Batteriekapazität

nom.

7Ah 26Ah/

750Wh

7)

Battery Current

for discharging

for

charging

Batteriestrom

bei Entladung

bei

Ladung

max.
max.

30A

1.8A

30A

11.5A

Battery Fuse

Batteriesicherung

ATO Fuse

30A

6)

30A

6)

Temperature Sensor

Temperaturfühler

-

No / Nein

No / Nein

Recommended Charging Voltage

Empfohlene Ladespannung

typ.

13.9V at 10°C, 13.75V at 20°C
13.6V at 30°C, 13.45V at 40°C

13.9V at 10°C, 13.75V at 20°C
13.6V at 30°C, 13.45V at 40°C

Self-discharge rate

Selbstentladungsrate

typ. at 20°C

3% / month

3% / month

Isolation Voltage between Power or
Signal Circuits to Chassis

Isolationsspannung zw. Leistungs-
oder Signalkreisen zum Gehäuse

max.

1100Vac 1100Vac

Temperature Range for discharging

for

charging

Temperaturbereich

bei Entladung

bei

Ladung

nom.
nom.

-15°C - +50°C

-10°C - +40°C

4)

-20°C - +60°C

-15°C - +50°C

4)

Storage Temperature Range

Lagertemperaturbereich

nom.

-20°C - +50°C

-20°C - +50°C

Humidity

5)

Feuchte

5)

IEC 60068-2-30

5 – 95% r.H.

5 – 95% r.H.

Vibration Schwingen IEC 60068-2-6

±4mm at 16.7Hz fixed frequency for 1hour

3)

/

±4mm bei 16.7Hz Festfrequenz für 1 Stunde

3)

±4mm at 16.7Hz fixed frequency for 1hour

3)

/

±4mm bei 16.7Hz Festfrequenz für 1 Stunde

3)

Shock Schocken

IEC 60068-2-27

free fall from 20cm onto a wooden floor

3)

/

Freier Fall von 20cm auf Holzplatte

3)

free fall from 20cm onto a wooden floor

3)

/

Freier Fall von 20cm auf Holzplatte

3)

Degree of Pollution

Verschmutzungsgrad

IEC 62103

2

2

Degree of Protection

Schutzart

EN 60529

IP00

IP00

Class of Protection

Schutzklasse

IEC 61140

III

III

Parallel Use

Parallel schaltbar

-

No / Nein

No / Nein

DIN-Rail Mounting

DIN-Schienen Montage

Yes / Ja

No / Nein

Flange Mounting

Wandmontage

Yes / Ja

Yes / Ja

Dimensions (WxHxD) Abmessungen

(BxHxT)

nom.

155x124x112mm (6.1’’x4.88’’x4.41’’)

214x179x158mm (8.43’’x7.05’’x6.22’’)

Weight Gewicht

max.

UZK: 3200g, 7.6lb / UZO: 550g, 1.21lb

UZK: 9000g, 19.8lb / UZO: 620g, 1.37lb

Battery Replacement

Ersatzbatterien

1x UZB12.071

1x UZB12.261

Limited Warranty

Gewährleistung

Years / Jahre

3

8)

3

8)

1) All parameters are specified at 25°C ambient temperature unless otherwise noted.
2) Battery module without installed battery
3) Vibration in vertical mounting orientation, shock with bottom down orientation;

according to IEC/EN 61056-1

4) Frequently charging below +5°C reduces the lifetime of the battery
5) Do not energize while condensation is present.
6) 30A fuse ATOF® 287 030 from Littelfuse. Must only be replaced with the same or an UL listed

fuse with the same nominal value and characteristics

7) Marking on the battery might show a Watt-hour rating instead of an Amp-hour rating
8) Except battery. Batteries are considered as a service part. Special conditions are part of our

general terms and conditions.

1) Alle Werte gelten bei 25°C Umgebungstemperatur, falls nichts anderes angegeben ist.
2) Batteriemodul

ohne

Batteriebestückung

3) Vibration in vertikaler Einbaulage, Schock mit dem Boden nach unten;

gemäß IEC/EN 61056-1

4) Häufiges Laden unterhalb +5°C verringert die Lebensdauer der Batterie
5) Nicht bei Betauung betreiben.
6) 30A

Sicherung

ATOF

®

287 030 von Littelfuse. Darf nur ersetzt werden durch dieselbe oder

eine vergleichbare UL gelistete Sicherung mit gleichen Nenndaten und Eigenschaften.

7) Anstelle von einer Ah Angabe kann an der Batterie auch eine Wh Angabe angebracht sein.
8) Ausgenommen Batterie. Batterien sind Verschleißteile, für die spezielle Bedingungen gelten.

Diese entnehmen Sie bitte aus unseren AGB.
















Fig. 3 / Bild 3

UZK12.261 Mechanical dimensions / Abmessungen

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: