1. General Information

Set Value Card +/-10V for the SK 500E series provides users with the possibility to control
the inverter through analogue bipolar set values (-10VDC ... +10VDC).

2. Assembly

The card is to be mounted separately from the inverter on a DIN rail within a
proper electrical cabinet (the card is IP00).

3. Function and parameter setting

The Set Value Card converts external bipolar signals (-10V...+10V) into
0...10VDC signals. For that, the input signal voltage level is inverted!
To operate properly, the inverter must be programmed for this!

Notice:

SK 500E frequency inverters frame size 5 or bigger, can be adjusted via a DIP-
switch for 0-10V or +/-10V set values, therefore it is not necessary to use the +/-
10V Set Value Card.

Parameter

[ Standard ]

Description

Settings for the

+/-10V Set Value Card

P400

Function analogue input 1

1

0 ... 82

[ 1 ]

1 =

Sollfrequenz, der angegebene Analogbereich (P402/P403) variiert die
Ausgangsfrequenz zwischen der eingestellten Minimal- und Maximalfrequenz
(P104/P105).

P401

Mode analogue input 1

1

0 ... 4

[ 0 ]

1 = 0

– 10V: A set point smaller that the programmed adjustment 0% (P402) does

not lead to undershooting of the programmed minimum frequency (P104). This
allows a change of the rotation direction.

P402

Adjust analogue input 1: 0%

5,0 ... 5,1

-50.00 ...
50.00V

[ 0.00 ]

Might be needed to adjust to  5,1V

P403

Adjust analogue input 1: 100%

0,0 ... 0,2

-50.00 ...
50.00V

[ 10.00 ]

Might be needed to adjust to  0,2V

P505

Absolute minimal frequency

2,0 ... 3,0

0.0 ... 10.0Hz

[ 2.0 ]

To get a wider hysteresis range on 0V, the absolute minimum frequency can be
adjusted here (maximal setting for the Set Value Card is 3,0Hz).