Wiring diagramm, Sk 500e – NORD Drivesystems BU0920 Benutzerhandbuch

Seite 3

Advertising
background image

+/-10V Set Value Card for SK 500E


BU 0920 GB

technical changes might be possible

3

Information

Parameter

Description

P709

Spannung Analogeingang 1

0.00 ... 10.00V

Show the measured analogue input 1 value.

4. Wiring diagramm

If the set value input (3) is not connected, the inverter might
read a meaningless voltage signal (> 0V).

Notice:

If the set value input (3) is not in use

– bridge the terminals 3

and 8.

The +/-10V set value input is specific to common ground level!

Shielded cables should be used, to ensure that set value volt-
age cannot be altered by external EMC.

+/-10V Set Value Card

11
12
14
16
17

21
22
23
24
25
42
40
41

AIN 1

AGND/0V

VO +10V

DIG 1

VO +15V

SK 500E

+/- 10 V

GND

Set Value
Source

X4

X5

5

6

7

8

VO 15V

GND/0V

VO 10V

GND/0V

4

3

2
2
2
7

1
8

n.c.

+/- 10V

n.c.

AIN 1

Advertising