Electrical connection – WIKA DIH62 Benutzerhandbuch

Seite 18

Advertising
background image

18

WIKA operating instructions models DIH50, DIH52, DIH62

GB

14008548.02 03/2012 GB/D

7.1 Field indicators models DIH50, DIH52

Open the case cover, push one of the two black fastening clips backwards and pull the

display module upwards. The power supply is connected at the front via the Philips screws

of the display module. Connect the positive pole of the power supply to the terminal marked

with ⊕ and the negative pole of the power supply to the terminal marked with ⊖.

The signal line of the transmitter is to be connected to the terminal blocks inside the field

case. To do so, connect the positive pole of the signal line to the terminal marked with ⊕

(red cable) and the negative pole of the signal line to the terminal marked with ⊖ (black

cable).

With flexible leads we recommend the use of crimped

connector sleeves.

The integrated reverse polarity protection (wrong polarity

on the terminals ⊕ and ⊖) prevents the digital indicator

from damage.

The following maximum values are applicable:

without explosion protection: 42 V

with explosion protection: 30 V

The connected wires must be checked to ensure they are connected properly. Only

well-secured wires can guarantee a fault-free operation.

Recommended tools for terminal screws:

Model

Screwdriver

Tightening torque

DIH50,

DIH52

Cross head ('Pozidriv' tip)

size 2 (ISO 8764)

0.4 Nm

7.2 Field indicator model DIH62

Open the case cover and remove the display and operation module by slightly turning it to

the left. Loosen the cable gland. Strip the signal lines approx. 10 cm and strip the insulation

of the wire ends approx. 1 cm. Connect the wire ends to the terminals according to the

connection diagram.

7. Electrical connection

Not Ex area

Ex area

black

spring-loaded

push terminals

Voltage supply

Load

Transmitter

DIH50, DIH52

red