WIKA operating instructions models DIH50, DIH52, DIH62

21

GB

14008548.02 03/2012 GB/D

8.1 Main menu "Measurement"

Function

Factory setting

Unit

Setting the unit of the measuring range of the connected transmitter
Setting range:

mA → Ω → bar → mbar → PSI → hPa → kPa → mmH

2

O → mH

2

O → inHG → °C →

°F → K → % → USER → V

mA

Measuring range start

Setting of the start value of the measuring range of the connected transmitter

(e.g. -30 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999

4,000

Measuring range end

Setting the end value of the measuring range of the connected transmitter

(e.g. 120 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999

20,000

Measuring range format

Setting the decimal point for the measuring range of the connected transmitter.
Setting range: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000

0.000

Span (only DIH52, DIH62)

The current measured value is applied as max. adjustment for the sensor.
Attention: Cannot be used for all HART

®

transmitters

-----

Zero point (only DIH52, DIH62)

The current measured value is applied as min. adjustment for the sensor.
Attention: Cannot be used for all HART

®

transmitters

-----

Damping (only DIH52, DIH62)

Input damping for damping the measured value.
Setting range: 0.0 … 999

0.0

Adress (only DIH52, DIH62)

Setting the HART

®

address of the assigned transmitter in the multidrop mode;

for the standard current loop mode, this address must always be set to 0.
Setting range: 0 ... 15

0