Electrical connection – WIKA TIF52 Benutzerhandbuch

Seite 21

Advertising
background image

WIKA operating instructions models TIF50, TIF52

21

GB

14009686.02 03/2012 GB/D

Maximum permissible load depending on the supply voltage:

Load diagram

11289130.02

Ex ia

1239
1152

717
456

0

0

13,5

24

30

40

42

For the power supply, use an energy-limited electrical circuit (EN/UL/IEC 61010-1,

section 8.3) using the following maximum values for the power supply:

for U

B

= 42 V (DC): 5 A

For the external power supply a separate switch is required.

The power supply is connected at the front via the Philips screws of the display

module. Connect the positive pole of the power supply to the terminal marked

with ⊕ and the negative pole of the power supply to the terminal marked with ⊖.

The signal line of the transmitter is to be connected to the terminal blocks inside the field

case. To do so, connect the positive pole of the signal line to the terminal marked with ⊕

(red cable) and the negative pole of the signal line to the terminal marked with ⊖ (black

cable).

DIH50-B

7. Electrical connection

With flexible leads we recommend the use of crimped

connector sleeves.

The integrated reverse polarity protection (wrong

polarity on the terminals ⊕ and ⊖) prevents the digital

indicator from damage.

Voltage U

B

in V

Load R

A

in Ω

Not Ex area

Ex area

Transmitter

red

black

Voltage supply

Load

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: