General rules for installation

In the installation of processor-controlled control systems, the following

principles must be observed:
1. If possible, do not allow any interference sources, i.e. implement

interference suppression and minimise the level of interference

(noise suppression in accordance with VDE 0875, implementation in

accordance with VDE 0874). In principle, eliminate an interference at

its point of generation. Introduce the suppression devices as close as

possible to the interference source.

2. Place unavoidable interference sources far away from the control

systems.

3. All sensor and signal wires must be separated from the powered and

mains wiring, in order to avoid capacitive or inductive coupling.

4. Use screened measuring cable, and ground the screen. Only provide

a single common ground connection, in order eliminate ground loops

and fault currents.

5. It is advisable to provide a separate power cable for the control

system's power supply, so that noise levels introduced via the power

cable are less strong and voltage drops when switching heavy loads

are less noticeable.

6. When switching inductive loads, cut out the resulting induction

voltages with protective elements, which will be different for direct and

alternating current systems.
In direct current systems, in the simplest case, a flyback diode with a

high surge current resistance can limit the induction voltage.

With alternating current operation, an RC filter is often used, which

is placed directly on the inductance and must be matched to it. The

determination of the filter values can made by calculation, if the

inductance of the coil is known, or experimentally. Only use approved

capacitors in accordance with VDE 0565.
The installation of an RC filter at the controller‘s switch contact is very

problematic, as even when the switch is open, a reactive current flows

through the filter. This may be greater than the holding current of the

contactor, whereby a closed contact will no longer open.