WIKA operating instructions models SC58, SC64

14054366.01 10/2012 GB/D

GB

7.1 First control level
Parameterisation of the set point

The set point, S1, is directly selectable by pressing the SET key. By then

pressing the UP or DOWN keys it can be set.

Para-

meters

Functional description

Setting

range

Standard

setting

S1

Set point, control contact 1

P4 ... P5

0.0 °C

7.2 Second control level (P parameter)
Setting of control parameters

By pressing the UP and DOWN keys simultaneously for at least

4 seconds one reaches the parameter list for control parameters

(beginning with P0).
The UP key scrolls the list up, the DOWN key scrolls it downwards. If one

presses the SET key, the value of the respective parameter is displayed.

By then pressing the UP or DOWN keys the value is adjusted.
After releasing all the keys, the new value will be stored permanently. If,

during 60 seconds, no key is pressed, there is an automatic return to the

initial position.

Para-

meters

Functional description

Setting range

Standard

setting

P0

Actual value

-

-

P2

Hysteresis K1

0.1 ... 99.9 K

1.0 K

P4*

Lower set-point limit

-99 °C ... P5

-99 °C

P5*

Upper set-point limit

P4 ... 999 °C

999 °C

P6

Actual value correction

-20.0 ... +20.0 K

0.0 K

P19

Key lock

0: not locked

1: locked

0

P30

Lower alarm limit

-99 ... 999 °C

-99 °C

P31

Upper alarm limit

-99 ... 999 °C

999 °C

P32

Hysteresis for alarm function 0.5 ... 99.9 K

1.0 K

d0

Defrost interval

0 ... 99 h

0 = no defrosting

0

7. Configuration