5

2 Safety notes

- The ambient temperatures must not exceed the limit values spec-

ified in the table below.

- The transmitter must be set up in such a way as to provide at

least IP20 protection according to EN 60529, also for the con-
necting parts.

- During setting up and operation of the transmitter, any build-up of

electrostatic charge must be avoided.

Extract from the Ex-specifications

Head-mounted

temperature transmitter 707015

II 1 G Ex ia IIC T6

Temperature range

in II 2 G

and II 3 G

T6: T

amb

= -40 to +55°C

T5: T

amb

= -40 to +70°C

T4: T

amb

= -40 to +75°C

Temperature range

in II 1 G

T6: T

amb

= -40 to +40°C

T5: T

amb

= -40 to +50°C

T4: T

amb

= -40 to +60°C

Supply circuit

maximum values at

terminals 1(+) and 2(-)

internal inductance

and capacitance

U

i

= 30VDC

I

i

= 100mA

P

i

= 750mW

L

i

= negligible

C

i

= negligible

Sensor current circuit

maximum values at

terminals 3, 4, 5 and 6

U

o

= 9.6VDC

I

o

= 4.5mA

P

o

= 11mW

max. permissible external

inductance/capacitance

Ex ia IIC

Ex ia IIB

L

o

= 4.5mH / C

o

= 709nF

L

o

= 8.5mH / C

o

= 1300nF

Advertising