10

5 Installation

Connection diagram

Connection for

Terminals

Supply
8 — 30V DC
or
current output
4 — 20mA

+1

-2

R

B

= burden resistance

U

b

= supply

Ex version only in combination with a certified Ex transmitter supply unit!

Analog inputs

Resistance
thermometer
in 4-wire circuit

3
4
5
6

R

L

11

R

L

= lead resistance

per conductor

Resistance
thermometer
in 3-wire circuit

3
5
6

R

L

11

R

L

= lead resistance

per conductor

Resistance
thermometer
in 2-wire circuit

3
6

R

L

11

R

L

= lead resistance

per conductor

Thermocouple

+4
-6

Ex version: please note the connection data for the Ex input circuit!

R

B

U

b

8V

22mA

-----------------

=

Advertising