GB ENGLISH

9

WORKING SETPOINTS AND CONFIGURATION PARAMETERS

9.1 Working setpoints

MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

r1

r2

°

C/°F (1) 0.0

working setpoint

9.2 Configuration parameters
PARAM. MIN.

MAX.

U.M.

DEF.

WORKING SETPOINTS

SP

r1

r2

°

C/°F (1) 0.0

working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MEASURE INPUTS

CA1

-25.0

25.0

°

C/°F (1) 0.0

room probe offset

P0

0

13

- - -

5

kind of probe
0 = PTC
1 = NTC
2 = J
3 = K
4 = 3 wires Pt 100
5 = 2 wires Pt 100
6 = 3 wires Pt 1000
7 = 2 wires Pt 1000
8 = 4-20 mA
9 = 0-20 mA
10 = 2-10 V
11 = 0-10 V
12 = 3 wires Ni 120
13 = 2 wires Ni 120

P1

0

1

- - -

1

if P0 = 0 ... 7 or 12 ... 13, decimal point Celsius
degree
1 = YES
if P0 = 8 ... 11, decimal point position
0 = no decimal point
1 = on the digit of ten

P2

0

2

- - -

0

unit of measure temperature (influential only on LED
Celsius degree and on LED Fahrenheit if
P0 = 8 ... 11) (2) (3)
0 = °C
1 = °F
2 = LED Celsius degree and LED Fahrenheit degree

will remain turned off

P3

-199.0 199.0 points

-20.0

minimum value of the range of the transducer

P4

-199.0 199.0 points

80.0

maximum value of the range of the transducer

P5

0

1

- - -

0

quantity to show during the normal operation
0 = room temperature
1 = working setpoint

PARAM. MIN.

MAX.

U.M.

DEF.

MAIN REGULATOR

r0

0.1

99.0

°

C/°F (1) 2.0

working setpoint differential

r1

-199.0 r2

°

C/°F (1) 0.0

minimum working setpoint

r2

r1

(4)

°

C/°F (1) 350.0 maximum working setpoint

r3

0

1

- - -

0

locking the working setpoint modification (with the
procedure related in paragraph 4.1)
1 = YES

r4

-99.0

99.0

°

C/°F (1) 0.0

temperature variation during function Energy Sav-
ing; also look at i5

r5

0

1

- - -

(5)

cooling or heating action
0 = cooling

PARAM. MIN.

MAX.

U.M.

DEF.

LOAD PROTECTIONS

C1

0

240

min

0

minimum time between two activations in succes-
sion of the load; also load delay since the end of
the room probe error (6)

C2

0

240

min

0

minimum time the load remains turned off; also load
delay since you turn on the instrument

C3

0

240

s

0

minimum time the load remains turned on

C4

0

240

min

10

time the load remains turned off during the room
probe error; also look at C5

C5

0

240

min

10

time the load remains turned on during the room
probe error; also look at C4

PARAM. MIN.

MAX.

U.M.

DEF.

DEFROST (7)

d0

0

99

h

8

defrost interval (8)
0 = the defrost at intervals will never be activated

d3

0

99

min

0

defrost duration
0 = the defrost will never be activated

d4

0

1

- - -

0

defrost when you turn on the instrument
1 = YES

d5

0

99

min

0

defrost delay when you turn on the instrument (only
if d4 = 1)

d6

0

1

- - -

1

temperature shown during the defrost
0 = room temperature
1 = if to the defrost activation the room tempera-

ture is below “working setpoint + r0”, at most
“working setpoint + r0”; if to the defrost activa-
tion the room temperature is above “working
setpoint + r0”, at most the room temperature
to the defrost activation (9)

PARAM. MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A1

-199.0 (4)

°

C/°F (1) 0.0

temperature the first temperature alarm is activated;
also look at A3 (10)

A2

0

240

min

0

first temperature alarm delay (11)

A3

0

4

- - -

0

kind of first temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A1)
2 = absolute upper alarm (or A1)
3 = lower alarm relative to the working setpoint (or

"working setpoint - A1”; consider A1 without
sign, do not consider r4)

DE DEUTSCH

9

SET POINT ARBEIT UND
KONFIGURATIONSPARAMETER

9.1 Set Point Arbeit
SET POINT ARBEIT
Set Point Arbeit
9.2 Parametri di configurazione
SET POINT ARBEIT
Set Point Arbeit
MASSEINGÄNGE
Offset Umgebungssonde
Sondentyp
0 = PTC
1 = NTC
2 = J
3 = K
4 = Pt 100 3 Drähte
5 = Pt 100 2 Drähte
6 = Pt 1000 3 Drähte
7 = Pt 1000 2 Drähte
8 = 4-20 mA
9 = 0-20 mA
10 = 2-10 V
11 = 0-10 V
12 = Ni 120 3 Drähte
13 = Ni 120 2 Drähte
wenn P0 = 0 ... 7 oder 12 ... 13, Dezimalpunkt Grad
Celsius
1 = JA
wenn P0 = 8...11, Position des Dezimalpunktes
0 = kein Dezimalpunkt
1 = auf digit der Zehner
Temperaturmesswert (wirkt nur auf der LED Grad
Celsius und der LED Grad Fahrenheit wenn
P0 = 8 ... 11) (2) (3)
0 = °C
1 = °F
2 = LED Grad Celsius LED Grad Fahrenheit bleiben

aus

Mindesteichwert des Wandlers
Maximaler Eichwert des Wandlers
dargestellte Größe während dem normalen Betrieb
0 = Umgebungstemperatur
1 = Set Point Arbeit
HAUPTREGLER
Differenzial des Set Points Arbeit
Minimum Set Point Arbeit
Maximum Set Point Arbeit
Sperre der Änderung Set Point Arbeit (mit der in
Absatz 4.1 angegebenen Prozedur)
1 = JA
Temperaturänderung während der Funktion Energy
Saving; siehe auch i5
funzionamento per freddo o per caldo
0 = für kalt
LADUNGSSCHUTZ
Mindestzeit zwischen zwei aufeinanderfolgenden
Starts der Ladung; auch Verzögerung der Ladung
vom Ende des Fehlers der Umgebungssonde (6)
Mindestdauer des Abschaltens der Ladung; auch
Verzögerung der Ladung beim Einschalten des Instrumentes
Mindestdauer des Einschaltens der Ladung
Dauer des Abschaltens der Ladung während dem
Fehler der Umgebungssonde; siehe auch C5
Dauer des Einschaltens der Ladung während dem
Fehler der Umgebungssonde; siehe auch C4
ENTFROSTUNG (7)
Entfrostungsintervall (8)
0 = Entfrosten mit Intervallen wird nie aktiviert
Dauer der Entfrostung
0 = Entfrosten wird nie aktiviert
Entfrosten beim Einschalten des Instrumentes
1 = JA
Verzögerung beim Entfrosten beim Einschalten des
Instrumentes (nur wenn d4 = 1)
Temperatur dargestellt während dem Entfrosten
0 = Umgebungstemperatur
1 = wenn bei Aktivierung des Entfrostens die

Umgebungstemperatur unter dem “Set Point
Arbeit + r0” liegt, höchstens “Set Point Arbeit +
r0”; wenn bei Aktivierung des Entfrostens die
Umgebungstemperatur über dem “Set Point
Arbeit + r0” liegt, höchstens bei Umgebungs-
temperatur bei Aktivierung des Entfrostens (9)

TEMPERATURALARME
Temperatur, bei der der erste Temperaturalarm
ausgelöst wird, siehe auch A3 (10)
Verzögerung erster Temperaturalarm (11)
Typ erster Temperaturalarm
0 = kein Alarm
1 = absolutes Minimum (oder A1)
2 = absolutes Maximum (oder A1)
3 = relatives Minimum bei Set Point Arbeit (oder “Set

Point Arbeit - A1”; A1 ohne Zeichen betrachten,
r4 nicht beachten)

4 = upper alarm relative to the working setpoint (or

"working setpoint + A1”; consider A1 without
sign, do not consider r4)

A4

0

240

min

0

temperature alarms delay since the working setpoint
modification (11)

A5

-199.0 (4)

°

C/°F (1) 0.0

temperature the second temperature alarm is acti-
vated; also look at A7 (10)

A6

0

240

min

0

second temperature alarm delay (11)

A7

0

4

- - -

0

kind of second temperature alarm
0 = alarm not enabled
1 = absolute lower alarm (or A5)
2 = absolute upper alarm (or A5)
3 = lower alarm relative to the working setpoint (or

"working setpoint - A5”; consider A5 without
sign)

4 = upper alarm relative to the working setpoint (or

"working setpoint + A5”; consider A5 without
sign)

PARAM. MIN.

MAX. U.M.

DEF.

DIGITAL INPUTS

i1

0

1

- - -

0

kind of contact digital input
0 = NO (input active if you close the contact)
1 = NC (input active if you open the contact)

i5

0

3

- - -

0

effect provoked by the activation of the multipur-
pose input
0 = no effect
1 = ACTIVATING THE EXTERNAL ALARM - spent the

time i7 the display will show the code “iA” flash-
ing and the buzzer will be activated (as long as
the input will be deactivated)

2 = LOAD PROTECTION - the load will be turned

off, the display will show the code “iA” flash-
ing and the buzzer will be activated (as long as
the input will be deactivated)

3 = ACTIVATING THE ENERGY SAVING - function

Energy Saving will be activated (as long as the
input will be deactivated); also look at r4 (12)

i7

0

120

min

0

if i5 = 1, delay to signal the multipurpose input alarm
if i5 = 2, load delay since the deactivation of the
multipurpose input

PARAM. MIN.

MAX. U.M.

DEF.

SERIAL NETWORK (MODBUS)

LA

1

247

- - -

247

instrument address

Lb

0

3

- - -

2

baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud

LP

0

2

- - -

2

parity
0 = none
1 = odd
2 = even

PARAM. MIN.

MAX. U.M.

DEF.

RESERVED

E9

0

1

- - -

1

reserved

(1)

the unit of measure depends on parameter P2

(2)

set the parameters related to the regulators appropriately after the
modification of the parameter P2

(3)

if parameter P0 has value 0 ... 7 or 12 ... 13 and parameter P2 has value 2, the
instrument will work as if parameter P2 had value 0

(4)

the value depends on parameter P2 (1,300 °C or 1,999 °F)

(5)

the value depends on the instrument code, as follows:

The question mark (?) replaces one field, the asterisk (*) replaces one or
more fields (or no-one); the field C means cooling, the field H means heating

(6)

if parameter C1 has value 0, the delay since the end of the room probe error will
however be 2 min

(7)

if parameter r5 has value 1 (heating action), the defrost functions will not be enabled

(8)

the instrument stores the count of the defrost interval every 30 min; the modification of
parameter d0 has effect since the end of the previous defrost interval or since the
activation of a defrost by hand

(9)

the display restores the normal operation as soon as the defrost ends and the room
temperature falls below the one that has locked the display (or if a temperature alarm
arises)

(10)

the differential depends on parameter P0 (2.0 °C/4 °F if parameter P0 has value 0 ... 7
or 12 ... 13, 2% of P4 - P3 if parameter P0 has value 8 ... 11)

(11)

during the defrost the temperature alarms are not enabled, on condition that they have
arisen after the activation of the defrost

(12)

the effect is not signalled.

4 = relatives Maximum bei Set Point Arbeit (oder “Set

Point Arbeit + A1”; A1 ohne Zeichen betrachten,
r4 nicht beachten)

Verzögerung Temperaturalarme von der Änderung
des Set Point Arbeit (11)
Temperatur, bei der der zweite Temperaturalarm
ausgelöst wird, siehe auch A7 (10)
Verzögerung zweiter Temperaturalarm (11)
Typ zweiter Temperaturalarm
0 = kein Alarm
1 = absolutes Minimum (oder A5)
2 = absolutes Maximum (oder A5)
3 = relatives Minimum bei Set Point Arbeit (oder

“Set Point Arbeit - A5”; A5 ohne Zeichen
betrachten)

4 = relatives Maximum bei Set Point Arbeit (oder

“Set Point Arbeit + A5”; A5 ohne Zeichen
betrachten)

DIGITALE EINGÄNGE
tipo di contatto dell’ingresso digitale
0 = NA (ingresso attivo con contatto chiuso)
1 = NC(Eingang aktiv bei offenem Kontakt)
Wirkung durch Aktivierung des multifunktionellen
Eingangs verursacht
0 = keine Wirkung
1 = AKTIVIERUNG AUSSENALARM - ist die Zeit i7

abgelaufen, zeigt das Display den Code “iA”
blinkend und der Summer wird aktiviert (bis der
Eingang deaktiviert wird)

2 = LADUNGSSCHUTZ - ist die Ladung abgeschal-

tet, zeigt das Display den Code “iA” blinkend
und der Summer wird aktiviert (bis der Eingang
deaktiviert wird)

3 = AKTIVIERUNG ENERGY SAVING - es wird die

Funktion Energy Saving aktiviert (bis der
Eingang deaktiviert wird); siehe auch r4 (12)

wenn i5 = 1, Verzögerung Alarmmeldung
multifunktioneller Eingang
wenn i5 = 2, Verzögerung Ladung von
Deaktivierung des multifunktioneller Eingangs
SERIELLES NETZ (MODBUS)
Adresse Instrument
baudrate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
Gleichstand
0 = kein Gleichstand
1 = ungleich
2 = gleich
RESERVIERT
reserviert
(1) die Messeinheit hängt vom Parameter P2 ab
(2) entsprechend die Parameter der Regler

nach der Änderung des Parameters P2
einstellen

(3) wenn Parameter P0 eingestellt ist auf 0...7 oder

auf 12...13 und der Parameter P2 ist auf 2,
funktioniert das Instrument als wäre der
Parameter P2 auf 0 eingestellt

(4) der Wert hängt vom Parameter P2 ab (1.300

°

C oder 1.999 °F)

(5) der Wert hängt vom Instrumentencode ab, im

angegebenen Modus:

Das Fragezeichen (?) ersetzt ein Feld,
der Stern (*) ersetzt ein oder mehrere
Felder (oder keines); das Feld C bedeutet
cooling (für kalt), das Feld H bedeutet heating
(für warm)

(6) ist der Parameter C1 auf 0 eingestellt, bleibt

die Verzögerung vom Ende des Fehlers der
Umgebungssonde 2 min.

(7) ist der Parameter r5 auf 1 eingestellt

(Warmbetrieb), sind die Funktionen zum
Entfrosten nicht freigegeben

(8) das Instrument speichert das Zählen des

Entfrostungsintervalls alle 30 min.; die
Änderung des Parameters d0 hat zum Ende
des vorigen Entfrostungsintervalls Wirkung
oder ab der Aktivierung des manuellen
Entfrostens

CODE
EV6421???C*

EV6421??
EV6421???
EV6421???H?*

WERT
r5 = 0 (für kalt)

r5 = 1 (für warm)
r5 = 1 (für warm)
r5 = 1 (für warm)

CODE
EV6421???C*

EV6421??
EV6421???
EV6421???H?*

VALUE
r5 = 0 (cooling)

r5 = 1 (heating)
r5 = 1 (heating)
r5 = 1 (heating)

(9) das Display stellt den normalen Betrieb wieder

her, wenn die Entfrostung zu Ende ist und die
Umgebungstemperatur unter der geht, die das
Display blockiert hat (oder wenn ein
Temperaturalarm besteht)

(10) das Differenzial hängt vom Parameter P0 (2,0

°

C/4 °F ab, wenn der Parameter P0 eingestellt

ist auf 0 ... 7 oder auf 12 ... 13, 2% von P4 -
P3, wenn der Parameter P0 eingestellt ist auf
8 ... 11)

(11) während dem Entfrosten gibt es keine

Temperaturalarme, unter der Bedingung, dass
diese nach der Aktivierung des Entfrostens auf-
getreten sind

(12) die Wirkung wird nicht gemeldet.