Warning: The unit must be permanently connected to the protective ground before operation. The
cross-sectional area of the protective earthing / grounding conductor shall be at least 10 mm
2
or
6 AWG.
Warnung: Diese Anlage muss vor der Inbetriebnahme ständig an den Schutzleiter angeschlossen
werden. Die Querschnittsfläche des Schutzerdungsleiters soll mindestens 10 mm
2
oder 6 AWG
betragen.
警告:进行设备操作前,请确保设备永久接地,并且确保接地线截面不小于
10 mm
2
或6 AWG。
Warning: Before the power cable is connected, it must be confirmed that the power cord complies
with the requirements of the actual installation (see power cord table)
Warnung: Überprüfen Sie vor dem Anbringen der Zuleitung immer, ob das von Ihnen verwendete
Kabel den Anforderungen entspricht (siehe Netzkabel-Tabelle).
警告
: 在进行电源线连接前,请确保电源线与实际安装要求一致(参考电源线表格)。
Warning Power Cord Table:
The power cord set must be approved for the country where it is used.
WARNUNG Netzkabel Tabelle:
Das Netzkabel muss für das Land, in dem es verwendet wird, zugelassen werden.
警告:电源线表格:
电源线组件必须满足使用的国家认证要求。
U.S.A. and
Canada
•
The cord set must be UL approved and CSA certified
•
The minimum specification for the flexible cord is:
•
No. 14 AWG
•
Type SV / SVT or SJ / SJT or SPT-2
•
3 conductor
•
The cord set must have a rated current carrying capacity of at least 20A.
•
The attachment plug must be an earth-grounding type with a NEMA 5-20
(20A, 125V) or NEMA 6-20 (20A, 250V) configuration
United Kingdom
•
The supply plug must be a 2 pole plug with dual earth contacts as per
IEC 60309.
•
The mains cord must <HAR> or <BASEC> marked and be of type
H05VVF3G1.50 (minimum)
Europe
•
The supply plug must comply with CEE 7/7 (“SCHUKO”)
•
The mains cord must <HAR> or <BASEC> marked and be of type
H05VVF3G1.50 (minimum)
Denmark
•
The supply plug must comply with the Heavy Current Regulations, section
107-2-D1 or EN60309-2.
Switzerland
•
The supply plug must comply with SEV/ASE 1011
Argentina
•
The power cord set must be certified by UL, IRAM, TÜV (or other
authorized certification body), for three conductors cables.
•
The attachment plug must be an earth-grounding type with an
IRAM-2073 (20 A, 250 V).
中国
•
电源线组件必须通过
CCC 认证。
•
必须使用符合
GB1002,额定值为 250V/16A 的单相两级带接地插头
•
电源线最小线径为
1.5mm
2
The appliance coupler (the connector to the unit and not the connector to the wall plug) must have a
configuration for mating with an EN 60320 / IEC 320 C19 appliance inlet.