Connecting the dc cables, Configuring the sunny backup system, Switching on the sunny backup system – SMA BACKUP 5000 Benutzerhandbuch

Seite 8

Advertising
background image

SMA Solar Technology AG

SBU-Li-Bat_B-IA-IXX121411

8/8

Connecting the DC Cables

1. Ensure that the DC connection requirements described by the battery manufacturer

(e.g. external fuses) are met (see installation manual of the lithium-ion battery).

2. Connect the DC cables to the backup inverter (for DC connection, see the technical description

of the SBU 5000 / Sunny Backup System S).

Configuring the Sunny Backup System

1. Switch the battery on (see installation manual of the lithium-ion battery).
2. Start the Quick Configuration Guide and configure the backup system in accordance with the

backup inverter manual (see technical description of the SBU 5000 / Sunny Backup System S).
Set the following parameters for the battery:
• Select the parameter BatTyp and set to battery type Li-Ion. This deactivates the battery

management of the backup inverter and the battery is controlled by its own battery
management.

• Select the parameter BatChrgVtgMan and set to the nominal charge voltage (for nominal

charge voltage, see installation manual of the lithium-ion battery).

• Select the parameter BatChrgCurMax and set to the charge current limitation (for charge

current limitation, see installation manual of the lithium-ion battery).

• Select the parameter BatDiChgVtg and set to the final cut-off voltage (for final cut-off

voltage, see installation manual of the lithium-ion battery).

• Select the parameter BatDiChgVtgSt and set to the reactivation voltage (activation voltage

after disconnection resulting from final cut-off voltage (hysteresis), see the installation manual
of the lithium-ion battery).

• Select the parameter BatDiChgCurMax and set to the discharge current limitation

(for discharge current limitation, see installation manual of the lithium-ion battery).

Switching on the Sunny Backup System

1. Switch the battery on (see installation manual of the lithium-ion battery).
2. Switch the Sunny Backup system on (see the technical description of the SBU 5000 /

Sunny Backup System S).

Advertising
Dieses Handbuch ist für die folgenden Produkte bezogen werden: