Operation, Voltage-thresholds tab sensitivity tab – MGE UPS Systems 1500 Rack Benutzerhandbuch

Seite 22

Advertising
background image

34007117EN/AB

- Page 21

3. Operation

Configurable function

Output voltage on battery power

Upper threshold for transfer to battery power

Fader-mode cut-in threshold

Booster-mode cut-in threshold

Lower threshold for transfer to battery power

Maximum input-voltage range

Default setting

230 V

294 V

265 V

184 V

160 V

Disabled

Options

200 V - 220 V - 240 V

271 to 294 V

244 to 265 V

184 to 207 V

160 to 180 V

Enabled

(1)

Configurable function

UPS sensitivity level

Default setting

Normal

Options

High or low

Voltage-thresholds tab

Sensitivity tab

For more informations about these settings, refer to the Help function of the "UPS Driver" software.

(1) Lower threshold for transfer to battery power = 150 V